Overview implemented RTD transformations

Some Beckhoff IO devices (IP20 terminals, plug-in modules, box‑modules) support the evaluation of resistance sensors for temperature measurement (RTD) as Pt100, Pt1000, NTC1K etc.

The following are the characteristic curves partially implemented there depending on the device. The table values given are the basis for the evaluation in the device.

Version 2026-02

Pt-RTD

Values in Ω

Pt100

Pt1000

Pt500

Pt200

[°C] (ITS-90)

-200…+850°C

-200…+850°C

-200…+850°C

-200…+850°C

-200

18.520

185.200

92.600

37.040

-190

22.825

228.250

114.125

45.650

-180

27.096

270.960

135.480

54.192

-170

31.335

313.350

156.675

62.670

-160

35.543

355.430

177.715

71.086

-150

39.723

397.230

198.615

79.446

-140

43.876

438.760

219.380

87.752

-130

48.005

480.050

240.025

96.010

-120

52.110

521.100

260.550

104.220

-110

56.193

561.930

280.965

112.386

-100

60.256

602.560

301.280

120.512

-90

64.300

643.000

321.500

128.600

-80

68.325

683.250

341.625

136.650

-70

72.335

723.350

361.675

144.670

-60

76.328

763.280

381.640

152.656

-50

80.306

803.060

401.530

160.612

-40

84.271

842.710

421.355

168.542

-30

88.222

882.220

441.110

176.444

-20

92.160

921.600

460.800

184.320

-10

96.086

960.860

480.430

192.172

0

100.000

1,000.000

500.000

200.000

10

103.903

1,039.030

519.515

207.806

20

107.794

1,077.940

538.970

215.588

30

111.673

1,116.730

558.365

223.346

40

115.541

1,155.410

577.705

231.082

50

119.397

1,193.970

596.985

238.794

60

123.242

1,232.420

616.210

246.484

70

127.075

1,270.750

635.375

254.150

80

130.897

1,308.970

654.485

261.794

90

134.707

1,347.070

673.535

269.414

100

138.506

1,385.060

692.530

277.012

110

142.293

1,422.930

711.465

284.586

120

146.068

1,460.680

730.340

292.136

130

149.832

1,498.320

749.160

299.664

140

153.584

1,535.840

767.920

307.168

150

157.325

1,573.250

786.625

314.650

160

161.054

1,610.540

805.270

322.108

170

164.772

1,647.720

823.860

329.544

180

168.478

1,684.780

842.390

336.956

190

172.173

1,721.730

860.865

344.346

200

175.856

1,758.560

879.280

351.712

210

179.528

1,795.280

897.640

359.056

220

183.188

1,831.880

915.940

366.376

230

186.836

1,868.360

934.180

373.672

240

190.473

1,904.730

952.365

380.946

250

194.098

1,940.980

970.490

388.196

260

197.712

1,977.120

988.560

395.424

270

201.314

2,013.140

1,006.570

402.628

280

204.905

2,049.050

1,024.525

409.810

290

208.484

2,084.840

1,042.420

416.968

300

212.052

2,120.520

1,060.260

424.104

Pt-RTD (continuation)

Values in Ω

Pt100

Pt1000

Pt500

Pt200

[°C] (ITS-90)

-200…+850°C

-200…+850°C

-200…+850°C

-200…+850°C

310

215.608

2,156.080

1,078.040

431.216

320

219.152

2,191.520

1,095.760

438.304

330

222.685

2,226.850

1,113.425

445.370

340

226.206

2,262.060

1,131.030

452.412

350

229.716

2,297.160

1,148.580

459.432

360

233.214

2,332.140

1,166.070

466.428

370

236.701

2,367.010

1,183.505

473.402

380

240.176

2,401.760

1,200.880

480.352

390

243.640

2,436.400

1,218.200

487.280

400

247.092

2,470.920

1,235.460

494.184

410

250.533

2,505.330

1,252.665

501.066

420

253.962

2,539.620

1,269.810

507.924

430

257.379

2,573.790

1,286.895

514.758

440

260.785

2,607.850

1,303.925

521.570

450

264.179

2,641.790

1,320.895

528.358

460

267.562

2,675.620

1,337.810

535.124

470

270.933

2,709.330

1,354.665

541.866

480

274.293

2,742.930

1,371.465

548.586

490

277.641

2,776.410

1,388.205

555.282

500

280.978

2,809.780

1,404.890

561.956

510

284.303

2,843.030

1,421.515

568.606

520

287.616

2,876.160

1,438.080

575.232

530

290.918

2,909.180

1,454.590

581.836

540

294.208

2,942.080

1,471.040

588.416

550

297.487

2,974.870

1,487.435

594.974

560

300.754

3,007.540

1,503.770

601.508

570

304.010

3,040.100

1,520.050

608.020

580

307.254

3,072.540

1,536.270

614.508

590

310.487

3,104.870

1,552.435

620.974

600

313.708

3,137.080

1,568.540

627.416

610

316.918

3,169.180

1,584.590

633.836

620

320.116

3,201.160

1,600.580

640.232

630

323.302

3,233.020

1,616.510

646.604

640

326.477

3,264.770

1,632.385

652.954

650

329.640

3,296.400

1,648.200

659.280

660

332.792

3,327.920

1,663.960

665.584

670

335.932

3,359.320

1,679.660

671.864

680

339.061

3,390.610

1,695.305

678.122

690

342.178

3,421.780

1,710.890

684.356

700

345.284

3,452.840

1,726.420

690.568

710

348.378

3,483.780

1,741.890

696.756

720

351.460

3,514.600

1,757.300

702.920

730

354.531

3,545.310

1,772.655

709.062

740

357.590

3,575.900

1,787.950

715.180

750

360.638

3,606.380

1,803.190

721.276

760

363.674

3,636.740

1,818.370

727.348

770

366.699

3,666.990

1,833.495

733.398

780

369.712

3,697.120

1,848.560

739.424

790

372.714

3,727.140

1,863.570

745.428

Pt-RTD (continuation)

Values in Ω

Pt100

Pt1000

Pt500

Pt200

[°C] (ITS-90)

-200…+850°C

-200…+850°C

-200…+850°C

-200…+850°C

800

375.704

3,757.040

1,878.520

751.408

810

378.683

3,786.830

1,893.415

757.366

820

381.650

3,816.500

1,908.250

763.300

830

384.605

3,846.050

1,923.025

769.210

840

387.549

3,875.490

1,937.745

775.098

850

390.481

3,904.810

1,952.405

780.962

Ni-RTD

Values in Ω

Ni100

Ni120

Ni1000

Ni1000 TK5000

α according to DIN43760

typ. 6180 pmm/K

typ. 6720 pmm/K

typ. 6180 pmm/K

typ. 5000 pmm/K

[°C] (ITS-90)

-60..50°C

-60..320°C

-60..250°C

-30..160°C

-60

69.52

80.943

695.200

 

-50

74.255

87.011

742.550

 

-40

79.131

93.251

791.310

 

-30

84.146

99.667

841.460

871.690

-20

89.296

106.261

892.960

913.480

-10

94.582

113.038

945.820

956.240

0

100

120.000

1,000.000

1,000.000

10

105.552

127.151

1,055.520

1,044.790

20

111.236

134.494

1,112.360

1,090.650

30

117.056

142.033

1,170.560

1,137.620

40

123.011

149.772

1,230.110

1,185.710

50

129.105

157.712

1,291.050

1,234.950

60

135.34

165.859

1,353.400

1,285.450

70

141.721

174.214

1,417.210

1,337.150

80

148.25

182.783

1,482.500

1,390.120

90

154.934

191.567

1,549.340

1,444.390

100

161.779

200.572

1,617.790

1,500.000

110

168.789

209.798

1,687.890

1,556.980

120

175.972

219.251

1,759.720

1,615.370

130

183.335

228.934

1,833.350

1,675.190

140

190.887

238.850

1,908.870

1,736.470

150

198.635

249.002

1,986.350

1,799.270

160

206.589

259.394

2,065.890

1,863.600

170

214.758

270.029

2,147.580

 

180

223.153

280.911

2,231.530

 

190

231.783

292.042

2,317.830

 

200

240.66

303.427

2,406.600

 

210

249.795

315.069

2,497.950

 

220

259.2

326.971

2,592.000

 

230

268.887

339.136

2,688.870

 

240

278.868

351.569

2,788.680

 

250

289.156

364.271

2,891.560

 

260

 

377.247

 

 

270

 

390.501

 

 

280

 

404.035

 

 

290

 

417.853

 

 

300

 

431.958

 

 

310

 

446.354

 

 

320

 

461.044

 

 

KT/KTY-RTD

Values in Ω

KT100..

KTY81/82-110…

KTY81-121

KTY81-122

KTY81-151

KTY81-152

[°C] (ITS-90)

-50..150°C

-50..150°C

-50..150°C

-50..150°C

-50..150°C

-50..150°C

-50

518

515

510

520

502

528

-40

570

567

562

573

553

582

-30

625

624

617

630

608

639

-20

685

684

677

690

667

701

-10

748

747

740

755

729

766

0

815

815

807

823

794

835

10

886

886

877

895

864

908

20

961

961

951

971

937

985

30

1,040

1,040

1,029

1,050

1,014

1,066

40

1,123

1,122

1,111

1,134

1,094

1,150

50

1,209

1,209

1,196

1,221

1,178

1,239

60

1,300

1,299

1,286

1,312

1,266

1,331

70

1,394

1,392

1,378

1,406

1,357

1,427

80

1,492

1,490

1,475

1,505

1,453

1,527

90

1,594

1,591

1,575

1,607

1,551

1,631

100

1,700

1,696

1,679

1,713

1,654

1,738

110

1,810

1,805

1,786

1,823

1,759

1,850

120

1,923

1,915

1,896

1,934

1,867

1,963

130

2,041

2,023

2,003

2,044

1,973

2,074

140

2,128

2,124

2,103

2,146

2,071

2,178

150

2,235

2,211

2,189

2,233

2,156

2,266

NTC-RTD

Values in Ω

NTC 1k8

NTC 1k8

NTC 2k2

NTC 3k

NTC 5k

NTC 10k

NTC 10k

NTC 10k

R0

R0=4940

R0=5200

R0=7373

R0=9822

R0=16325

R0=27280

R0=29490

R0=29588

C1 1)

1.25835E-03

1.09447E-03

1.46042E-03

1.39183E-03

1.28772E-03

9.01568E-04

1.02381E-03

1.00996E-03

C2 1)

2.69483E-04

3.06398E-04

2.39847E-04

2.39480E-04

2.35694E-04

2.49334E-04

2.39960E-04

2.42461E-04

C3 1)

 0

 0

 0

 0

 0

 0

 0

 0

C4 1)

1.79850E-07

-8.80292E-08

9.14512E-08

8.72452E-08

9.52328E-08

1.99664E-07

1.53713E-07

1.41928E-07

[°C] (ITS-90)

-40..130°C

-30..150°C

-50..130°C

-30..80°C

-40..100°C

-40..110°C

-30..150°C

-50..130°C

-50

 

 

154,464

205,800

333,914

329,200

441,300

454,910

-40

35,480

 

77,081

102,690

167,835.5

188,400

239,800

245,089

-30

20,659

24,500

40,330

53,730

88,341.5

111,300

135,200

137,307

-20

12,443

14,000

22,032

29,346

48,487

67,740

78,910

79,729

-10

7,730

8,400

12,519

16,674

27,649

42,250

47,540

47,843

0

4,940

5,200

7,373

9,822

16,325.4

27,280

29,490

29,588

10

3,241

3,330

4,487

5,976

9,951.75

17,960

18,790

18,813

20

2,177

2,200

2,814

3,750

6,246.85

12,090

12,260

12,272

25

1,800

1,800

2,252

3,000

5,000

10,000

10,000

10,000

30

1,496

1,480

1,814

2,417

4,028

8,310

8,190

8,195

40

1,049

1,040

1,199

1,598

2,662.45

5,820

5,590

5,593

50

750

740

811.5

1,081

1,800.5

4,160

3,890

3,894

60

545

540

561

747

1,243.55

3,020

2,760

2,763

70

403

402

395.5

527

875.8

2,220

1,990

1,994

80

303

306

284

378

628.09

1,660

1,460

1,462

90

230

240

207.4

 

458.06

1,260

1,080

1,088

100

178

187

153.8

 

339.32

970

820

821

110

139

149

115.8

 

255.03

750

620

628

120

110

118

88.3

 

194.3

 

480

486

130

87

95

68.3

 

149.91

 

380

380

140

71

77

 

 

117.04

 

300

 

150

 

64

 

 

92.4

 

240

 

1) Coefficient for the Steinhart-Hart equation

NTC-RTD (continuation)

Values in Ω

NTC 10k

NTC 10k

NTC 10k

NTC 10K

NTC 20K

NTC 100k

NTC 100k

R0

R0=32639

R0=32650

R0=32660

R0=32770

R0=70200

R0=326600

R0=327240

C1 1)

1.13048E-03

1.12119E-03

1.12715E-03

1.11312E-03

1.15399E-03

6.09783E-04

9.04083E-04

C2 1)

2.33905E-04

2.35346E-04

2.34458E-04

2.36910E-04

2.12816E-04

2.29282E-04

1.53712E-04

C3 1)

0

0

0

0

0

0

6.30765E-06

C4 1)

8.86105E-08

8.34620E-08

8.63055E-08

7.53186E-08

9.51018E-08

6.84669E-08

-1.02569E-07

[°C] (ITS-90)

-40..130°C

-30..150°C

-50..130°C

-50..130°C

-20..150°C

-40..130°C

-30..270°C

-50

 

667,830

672,300

692,700

1,667,570

 

 

-40

333,562

335,670

337,200

344,700

813,440

3,366,000

 

-30

176,081

176,680

177,200

180,100

415,480

1,770,000

1,733,200

-20

96,807

96,970

97,130

98,320

221,300

971,200

959,050

-10

55,252

55,300

55,340

55,790

122,470

553,400

551,410

0

32,639

32,650

32,660

32,770

70,200

326,600

327,240

10

19,901

19,900

19,900

19,930

41,560

199,000

199,990

20

12,493

12,490

12,490

12,500

25,350

124,900

125,245

25

10,000

10,000

10,000

10,000

20,000

100,000

100,000

30

8,055

8,060

8,056

8,055

15,890

80,580

81,000

40

5,324

5,320

5,326

5,323

10,210

53,260

53,500

50

3,600

3,600

3,602

3,599

6,720

36,020

35,899

60

2,486

2,490

2,489

2,486

4,520

24,880

25,000

70

1,751

1,750

1,753

1,753

3,100

17,510

17,550

80

1,255

1,260

1,258

1,258

2,120

12,560

12,540

90

915

920

917

919

1,540

9,164

9,100

100

678

680

679

682

1,120

6,792

6,710

110

509

510

511

513

820

5,108

5,070

120

388

390

389

392

610

3,894

3,850

130

299

300

301

303

460

3,006

2,940

140

 

230

 

 

350

 

2,271

150

 

180

 

 

270

 

1,770

160

 

 

 

 

 

 

1,414

170

 

 

 

 

 

 

1,122

180

 

 

 

 

 

 

896

190

 

 

 

 

 

 

719

200

 

 

 

 

 

 

582

210

 

 

 

 

 

 

483

220

 

 

 

 

 

 

396

230

 

 

 

 

 

 

328

240

 

 

 

 

 

 

273.7

250

 

 

 

 

 

 

230

260

 

 

 

 

 

 

194.6

270

 

 

 

 

 

 

165.6

280

 

 

 

 

 

 

141.7

290

 

 

 

 

 

 

122

300

 

 

 

 

 

 

105.6

1) Coefficient for the Steinhart-Hart equation