Type D, E, G, J, K, L
|
Values in µV |
|
Type E |
|
Type J |
Type K |
Type L |
|---|---|---|---|---|---|---|
|
[°C] |
|
‑270…‑10°C |
|
‑210…‑10°C |
‑270…‑10°C |
‑50…‑10°C |
|
-270 |
|
-9,835 |
|
|
-6,458 |
|
|
-260 |
|
-9,797 |
|
|
-6,441 |
|
|
-250 |
|
-9,718 |
|
|
-6,404 |
|
|
-240 |
|
-9,604 |
|
|
-6,344 |
|
|
-230 |
|
-9,455 |
|
|
-6,262 |
|
|
-220 |
|
-9,274 |
|
|
-6,158 |
|
|
-210 |
|
-9,063 |
|
-8,095 |
-6,035 |
|
|
-200 |
|
-8,825 |
|
-7,890 |
-5,891 |
|
|
-190 |
|
-8,561 |
|
-7,659 |
-5,730 |
|
|
-180 |
|
-8,273 |
|
-7,403 |
-5,550 |
|
|
-170 |
|
-7,963 |
|
-7,123 |
-5,354 |
|
|
-160 |
|
-7,632 |
|
-6,821 |
-5,141 |
|
|
-150 |
|
-7,279 |
|
-6,500 |
-4,913 |
|
|
-140 |
|
-6,907 |
|
-6,159 |
-4,669 |
|
|
-130 |
|
-6,516 |
|
-5,801 |
-4,411 |
|
|
-120 |
|
-6,107 |
|
-5,426 |
-4,138 |
|
|
-110 |
|
-5,681 |
|
-5,037 |
-3,852 |
|
|
-100 |
|
-5,237 |
|
-4,633 |
-3,554 |
|
|
-90 |
|
-4,777 |
|
-4,215 |
-3,243 |
|
|
-80 |
|
-4,302 |
|
-3,786 |
-2,920 |
|
|
-70 |
|
-3,811 |
|
-3,344 |
-2,587 |
|
|
-60 |
|
-3,306 |
|
-2,893 |
-2,243 |
|
|
-50 |
|
-2,787 |
|
-2,431 |
-1,889 |
-2,510 |
|
-40 |
|
-2,255 |
|
-1,961 |
-1,527 |
-2,030 |
|
-30 |
|
-1,709 |
|
-1,482 |
-1,156 |
-1,530 |
|
-20 |
|
-1,152 |
|
-995 |
-778 |
-1,020 |
|
-10 |
|
-582 |
|
-501 |
-392 |
-510 |
Continuation type D, E, J, K, L
|
Values in µV |
Type D |
Type E |
|
Type J |
Type K |
Type L |
|---|---|---|---|---|---|---|
|
[°C] |
0…490°C |
0…490°C |
|
0…490°C |
0…490°C |
0…490°C |
|
0 |
0 |
0 |
|
0 |
0 |
0 |
|
10 |
97 |
591 |
|
507 |
397 |
520 |
|
20 |
199 |
1,192 |
|
1,019 |
798 |
1,050 |
|
30 |
305 |
1,801 |
|
1,537 |
1,203 |
1,580 |
|
40 |
414 |
2,420 |
|
2,059 |
1,612 |
2,110 |
|
50 |
527 |
3,048 |
|
2,585 |
2,023 |
2,650 |
|
60 |
644 |
3,685 |
|
3,116 |
2,436 |
3,190 |
|
70 |
764 |
4,330 |
|
3,650 |
2,851 |
3,730 |
|
80 |
888 |
4,985 |
|
4,187 |
3,267 |
4,270 |
|
90 |
1,015 |
5,648 |
|
4,726 |
3,682 |
4,820 |
|
100 |
1,145 |
6,319 |
|
5,269 |
4,096 |
5,370 |
|
110 |
1,278 |
6,998 |
|
5,814 |
4,509 |
5,920 |
|
120 |
1,414 |
7,685 |
|
6,360 |
4,920 |
6,470 |
|
130 |
1,553 |
8,379 |
|
6,909 |
5,328 |
7,030 |
|
140 |
1,695 |
9,081 |
|
7,459 |
5,735 |
7,590 |
|
150 |
1,840 |
9,789 |
|
8,010 |
6,138 |
8,150 |
|
160 |
1,987 |
10,503 |
|
8,562 |
6,540 |
8,710 |
|
170 |
2,137 |
11,224 |
|
9,115 |
6,941 |
9,270 |
|
180 |
2,289 |
11,951 |
|
9,669 |
7,340 |
9,830 |
|
190 |
2,444 |
12,684 |
|
10,224 |
7,739 |
10,390 |
|
200 |
2,602 |
13,421 |
|
10,779 |
8,138 |
10,950 |
|
210 |
2,761 |
14,164 |
|
11,334 |
8,539 |
11,510 |
|
220 |
2,923 |
14,912 |
|
11,889 |
8,940 |
12,070 |
|
230 |
3,086 |
15,664 |
|
12,445 |
9,343 |
12,630 |
|
240 |
3,252 |
16,420 |
|
13,000 |
9,747 |
13,190 |
|
250 |
3,420 |
17,181 |
|
13,555 |
10,153 |
13,750 |
|
260 |
3,590 |
17,945 |
|
14,110 |
10,561 |
14,310 |
|
270 |
3,761 |
18,713 |
|
14,665 |
10,971 |
14,880 |
|
280 |
3,934 |
19,484 |
|
15,219 |
11,382 |
15,440 |
|
290 |
4,109 |
20,259 |
|
15,773 |
11,795 |
16,000 |
|
300 |
4,286 |
21,036 |
|
16,327 |
12,209 |
16,560 |
|
310 |
4,464 |
21,817 |
|
16,881 |
12,624 |
17,120 |
|
320 |
4,644 |
22,600 |
|
17,434 |
13,040 |
17,680 |
|
330 |
4,825 |
23,386 |
|
17,986 |
13,457 |
18,240 |
|
340 |
5,007 |
24,174 |
|
18,538 |
13,874 |
18,800 |
|
350 |
5,191 |
24,964 |
|
19,090 |
14,293 |
19,360 |
|
360 |
5,376 |
25,757 |
|
19,642 |
14,713 |
19,920 |
|
370 |
5,563 |
26,552 |
|
20,194 |
15,133 |
20,480 |
|
380 |
5,750 |
27,348 |
|
20,745 |
15,554 |
21,040 |
|
390 |
5,939 |
28,146 |
|
21,297 |
15,975 |
21,600 |
|
400 |
6,129 |
28,946 |
|
21,848 |
16,397 |
22,160 |
|
410 |
6,320 |
29,747 |
|
22,400 |
16,820 |
22,720 |
|
420 |
6,512 |
30,550 |
|
22,952 |
17,243 |
23,290 |
|
430 |
6,704 |
31,354 |
|
23,504 |
17,667 |
23,860 |
|
440 |
6,898 |
32,159 |
|
24,057 |
18,091 |
24,430 |
|
450 |
7,093 |
32,965 |
|
24,610 |
18,516 |
25,000 |
|
460 |
7,288 |
33,772 |
|
25,164 |
18,941 |
25,570 |
|
470 |
7,484 |
34,579 |
|
25,720 |
19,366 |
26,140 |
|
480 |
7,681 |
35,387 |
|
26,276 |
19,792 |
26,710 |
|
490 |
7,878 |
36,196 |
|
26,834 |
20,218 |
27,280 |
Continuation type D, E, J, K, L
|
Values in µV |
Type D |
Type E |
|
Type J |
Type K |
Type L |
|---|---|---|---|---|---|---|
|
[°C] |
500…990°C |
500…990°C |
|
500…990°C |
500…990°C |
500…900°C |
|
500 |
8,076 |
37,005 |
|
27,393 |
20,644 |
27,850 |
|
510 |
8,275 |
37,815 |
|
27,953 |
21,071 |
28,430 |
|
520 |
8,474 |
38,624 |
|
28,516 |
21,497 |
29,010 |
|
530 |
8,674 |
39,434 |
|
29,080 |
21,924 |
29,590 |
|
540 |
8,874 |
40,243 |
|
29,647 |
22,350 |
30,170 |
|
550 |
9,075 |
41,053 |
|
30,216 |
22,776 |
30,750 |
|
560 |
9,276 |
41,862 |
|
30,788 |
23,203 |
31,330 |
|
570 |
9,478 |
42,671 |
|
31,362 |
23,629 |
31,910 |
|
580 |
9,680 |
43,479 |
|
31,939 |
24,055 |
32,490 |
|
590 |
9,883 |
44,286 |
|
32,519 |
24,480 |
33,080 |
|
600 |
10,085 |
45,093 |
|
33,102 |
24,905 |
33,670 |
|
610 |
10,288 |
45,900 |
|
33,689 |
25,330 |
34,260 |
|
620 |
10,491 |
46,705 |
|
34,279 |
25,755 |
34,850 |
|
630 |
10,695 |
47,509 |
|
34,873 |
26,179 |
35,440 |
|
640 |
10,899 |
48,313 |
|
35,470 |
26,602 |
36,040 |
|
650 |
11,102 |
49,116 |
|
36,071 |
27,025 |
36,640 |
|
660 |
11,307 |
49,917 |
|
36,675 |
27,447 |
37,240 |
|
670 |
11,511 |
50,718 |
|
37,284 |
27,869 |
37,850 |
|
680 |
11,715 |
51,517 |
|
37,896 |
28,289 |
38,470 |
|
690 |
11,919 |
52,315 |
|
38,512 |
28,710 |
39,090 |
|
700 |
12,124 |
53,112 |
|
39,132 |
29,129 |
39,720 |
|
710 |
12,329 |
53,908 |
|
39,755 |
29,548 |
40,350 |
|
720 |
12,533 |
54,703 |
|
40,382 |
29,965 |
40,980 |
|
730 |
12,738 |
55,497 |
|
41,012 |
30,382 |
41,620 |
|
740 |
12,942 |
56,289 |
|
41,645 |
30,798 |
42,270 |
|
750 |
13,147 |
57,080 |
|
42,281 |
31,213 |
42,920 |
|
760 |
13,352 |
57,870 |
|
42,919 |
31,628 |
43,570 |
|
770 |
13,556 |
58,659 |
|
43,559 |
32,041 |
44,230 |
|
780 |
13,761 |
59,446 |
|
44,203 |
32,453 |
44,890 |
|
790 |
13,965 |
60,232 |
|
44,848 |
32,865 |
45,550 |
|
800 |
14,170 |
61,017 |
|
45,494 |
33,275 |
46,220 |
|
810 |
14,375 |
61,801 |
|
46,141 |
33,685 |
46,890 |
|
820 |
14,580 |
62,583 |
|
46,786 |
34,093 |
47,570 |
|
830 |
14,784 |
63,364 |
|
47,431 |
34,501 |
48,250 |
|
840 |
14,989 |
64,144 |
|
48,074 |
34,908 |
48,940 |
|
850 |
15,193 |
64,922 |
|
48,715 |
35,313 |
49,630 |
|
860 |
15,397 |
65,698 |
|
49,353 |
35,718 |
50,320 |
|
870 |
15,601 |
66,473 |
|
49,989 |
36,121 |
51,020 |
|
880 |
15,804 |
67,246 |
|
50,622 |
36,524 |
51,720 |
|
890 |
16,008 |
68,017 |
|
51,251 |
36,925 |
52,430 |
|
900 |
16,211 |
68,787 |
|
51,877 |
37,326 |
53,140 |
|
910 |
16,414 |
69,554 |
|
52,500 |
37,725 |
|
|
920 |
16,616 |
70,319 |
|
53,119 |
38,124 |
|
|
930 |
16,819 |
71,082 |
|
53,735 |
38,522 |
|
|
940 |
17,021 |
71,844 |
|
54,347 |
38,918 |
|
|
950 |
17,222 |
72,603 |
|
54,956 |
39,314 |
|
|
960 |
17,424 |
73,360 |
|
55,561 |
39,708 |
|
|
970 |
17,625 |
74,115 |
|
56,164 |
40,101 |
|
|
980 |
17,825 |
74,869 |
|
56,763 |
40,494 |
|
|
990 |
18,026 |
75,621 |
|
57,360 |
40,885 |
|
Continuation type D, E, G, J, K
|
Values in µV |
Type D |
Type E |
Type G |
Type J |
Type K |
|
|---|---|---|---|---|---|---|
|
[°C] |
1,000…1,490°C |
1,000°C |
1,000…1,490°C |
1,000…1,200°C |
1,000…1,370°C |
|
|
1,000 |
18,226 |
76,373 |
14,500 |
57,953 |
41,276 |
|
|
1,010 |
18,425 |
|
14,700 |
58,545 |
41,665 |
|
|
1,020 |
18,625 |
|
14,900 |
59,134 |
42,053 |
|
|
1,030 |
18,824 |
|
15,100 |
59,721 |
42,440 |
|
|
1,040 |
19,022 |
|
15,300 |
60,307 |
42,826 |
|
|
1,050 |
19,220 |
|
15,500 |
60,890 |
43,211 |
|
|
1,060 |
19,418 |
|
15,700 |
61,473 |
43,595 |
|
|
1,070 |
19,616 |
|
15,900 |
62,054 |
43,978 |
|
|
1,080 |
19,812 |
|
16,100 |
62,634 |
44,359 |
|
|
1,090 |
20,009 |
|
16,300 |
63,214 |
44,740 |
|
|
1,100 |
20,205 |
|
16,500 |
63,792 |
45,119 |
|
|
1,110 |
20,401 |
|
16,700 |
64,370 |
45,497 |
|
|
1,120 |
20,596 |
|
16,900 |
64,948 |
45,873 |
|
|
1,130 |
20,791 |
|
17,100 |
65,525 |
46,249 |
|
|
1,140 |
20,985 |
|
17,300 |
66,102 |
46,623 |
|
|
1,150 |
21,179 |
|
17,500 |
66,679 |
46,995 |
|
|
1,160 |
21,373 |
|
17,700 |
67,255 |
47,367 |
|
|
1,170 |
21,566 |
|
17,900 |
67,831 |
47,737 |
|
|
1,180 |
21,758 |
|
18,100 |
68,406 |
48,105 |
|
|
1,190 |
21,950 |
|
18,300 |
68,980 |
48,473 |
|
|
1,200 |
22,142 |
|
18,500 |
69,553 |
48,838 |
|
|
1,210 |
22,333 |
|
18,700 |
|
49,202 |
|
|
1,220 |
22,524 |
|
18,900 |
|
49,565 |
|
|
1,230 |
22,714 |
|
19,100 |
|
49,926 |
|
|
1,240 |
22,904 |
|
19,300 |
|
50,286 |
|
|
1,250 |
23,094 |
|
19,500 |
|
50,644 |
|
|
1,260 |
23,282 |
|
19,700 |
|
51,000 |
|
|
1,270 |
23,471 |
|
19,900 |
|
51,355 |
|
|
1,280 |
23,659 |
|
20,100 |
|
51,708 |
|
|
1,290 |
23,846 |
|
20,300 |
|
52,060 |
|
|
1,300 |
24,033 |
|
20,500 |
|
52,410 |
|
|
1,310 |
24,219 |
|
20,700 |
|
52,759 |
|
|
1,320 |
24,405 |
|
20,900 |
|
53,106 |
|
|
1,330 |
24,591 |
|
21,100 |
|
53,451 |
|
|
1,340 |
24,776 |
|
21,300 |
|
53,795 |
|
|
1,350 |
24,960 |
|
21,500 |
|
54,138 |
|
|
1,360 |
25,144 |
|
21,700 |
|
54,479 |
|
|
1,370 |
25,327 |
|
21,900 |
|
54,819 |
|
|
1,380 |
25,510 |
|
22,100 |
|
|
|
|
1,390 |
25,693 |
|
22,300 |
|
|
|
|
1,400 |
25,875 |
|
22,500 |
|
|
|
|
1,410 |
26,056 |
|
22,700 |
|
|
|
|
1,420 |
26,237 |
|
22,900 |
|
|
|
|
1,430 |
26,418 |
|
23,100 |
|
|
|
|
1,440 |
26,597 |
|
23,300 |
|
|
|
|
1,450 |
26,777 |
|
23,500 |
|
|
|
|
1,460 |
26,956 |
|
23,700 |
|
|
|
|
1,470 |
27,134 |
|
23,900 |
|
|
|
|
1,480 |
27,312 |
|
24,100 |
|
|
|
|
1,490 |
27,489 |
|
24,300 |
|
|
|
Continuation type D, G
|
Values in µV |
Type D |
|
Type G |
|
|
|
|---|---|---|---|---|---|---|
|
[°C] |
1,500…1,990°C |
|
1,500…1,990°C |
|
|
|
|
1,500 |
27,666 |
|
24,500 |
|
|
|
|
1,510 |
27,842 |
|
24,700 |
|
|
|
|
1,520 |
28,018 |
|
24,900 |
|
|
|
|
1,530 |
28,193 |
|
25,100 |
|
|
|
|
1,540 |
28,367 |
|
25,300 |
|
|
|
|
1,550 |
28,541 |
|
25,500 |
|
|
|
|
1,560 |
28,715 |
|
25,700 |
|
|
|
|
1,570 |
28,888 |
|
25,900 |
|
|
|
|
1,580 |
29,060 |
|
26,100 |
|
|
|
|
1,590 |
29,232 |
|
26,300 |
|
|
|
|
1,600 |
29,403 |
|
26,500 |
|
|
|
|
1,610 |
29,574 |
|
26,700 |
|
|
|
|
1,620 |
29,744 |
|
26,900 |
|
|
|
|
1,630 |
29,914 |
|
27,100 |
|
|
|
|
1,640 |
30,083 |
|
27,300 |
|
|
|
|
1,650 |
30,251 |
|
27,500 |
|
|
|
|
1,660 |
30,419 |
|
27,700 |
|
|
|
|
1,670 |
30,586 |
|
27,900 |
|
|
|
|
1,680 |
30,753 |
|
28,100 |
|
|
|
|
1,690 |
30,919 |
|
28,300 |
|
|
|
|
1,700 |
31,084 |
|
28,500 |
|
|
|
|
1,710 |
31,249 |
|
28,700 |
|
|
|
|
1,720 |
31,413 |
|
28,900 |
|
|
|
|
1,730 |
31,576 |
|
29,100 |
|
|
|
|
1,740 |
31,739 |
|
29,300 |
|
|
|
|
1,750 |
31,901 |
|
29,500 |
|
|
|
|
1,760 |
32,063 |
|
29,700 |
|
|
|
|
1,770 |
32,223 |
|
29,900 |
|
|
|
|
1,780 |
32,384 |
|
30,100 |
|
|
|
|
1,790 |
32,543 |
|
30,200 |
|
|
|
|
1,800 |
32,702 |
|
30,400 |
|
|
|
|
1,810 |
32,860 |
|
30,600 |
|
|
|
|
1,820 |
33,017 |
|
30,800 |
|
|
|
|
1,830 |
33,173 |
|
31,000 |
|
|
|
|
1,840 |
33,329 |
|
31,200 |
|
|
|
|
1,850 |
33,484 |
|
31,300 |
|
|
|
|
1,860 |
33,638 |
|
31,500 |
|
|
|
|
1,870 |
33,792 |
|
31,700 |
|
|
|
|
1,880 |
33,944 |
|
31,900 |
|
|
|
|
1,890 |
34,096 |
|
32,100 |
|
|
|
|
1,900 |
34,247 |
|
32,300 |
|
|
|
|
1,910 |
34,397 |
|
32,400 |
|
|
|
|
1,920 |
34,546 |
|
32,600 |
|
|
|
|
1,930 |
34,695 |
|
32,800 |
|
|
|
|
1,940 |
34,842 |
|
33,000 |
|
|
|
|
1,950 |
34,989 |
|
33,200 |
|
|
|
|
1,960 |
35,134 |
|
33,400 |
|
|
|
|
1,970 |
35,279 |
|
33,500 |
|
|
|
|
1,980 |
35,423 |
|
33,700 |
|
|
|
|
1,990 |
35,565 |
|
33,900 |
|
|
|
Continuation type D, G
|
Values in µV |
Type D |
|
Type G |
|
|
|
|---|---|---|---|---|---|---|
|
[°C] |
2,000…2,490°C |
|
2,000…2,300°C |
|
|
|
|
2,000 |
35,707 |
|
34,100 |
|
|
|
|
2,010 |
35,847 |
|
34,300 |
|
|
|
|
2,020 |
35,987 |
|
34,400 |
|
|
|
|
2,030 |
36,125 |
|
34,600 |
|
|
|
|
2,040 |
36,263 |
|
34,800 |
|
|
|
|
2,050 |
36,399 |
|
34,900 |
|
|
|
|
2,060 |
36,534 |
|
35,100 |
|
|
|
|
2,070 |
36,668 |
|
35,200 |
|
|
|
|
2,080 |
36,801 |
|
35,400 |
|
|
|
|
2,090 |
36,932 |
|
35,600 |
|
|
|
|
2,100 |
37,062 |
|
35,700 |
|
|
|
|
2,110 |
37,191 |
|
35,900 |
|
|
|
|
2,120 |
37,319 |
|
36,000 |
|
|
|
|
2,130 |
37,445 |
|
36,200 |
|
|
|
|
2,140 |
37,570 |
|
36,300 |
|
|
|
|
2,150 |
37,694 |
|
36,500 |
|
|
|
|
2,160 |
37,816 |
|
36,700 |
|
|
|
|
2,170 |
37,937 |
|
36,800 |
|
|
|
|
2,180 |
38,056 |
|
37,000 |
|
|
|
|
2,190 |
38,173 |
|
37,100 |
|
|
|
|
2,200 |
38,289 |
|
37,300 |
|
|
|
|
2,210 |
38,404 |
|
37,400 |
|
|
|
|
2,220 |
38,517 |
|
37,600 |
|
|
|
|
2,230 |
38,628 |
|
37,800 |
|
|
|
|
2,240 |
38,737 |
|
37,900 |
|
|
|
|
2,250 |
38,845 |
|
38,100 |
|
|
|
|
2,260 |
38,951 |
|
38,200 |
|
|
|
|
2,270 |
39,055 |
|
38,300 |
|
|
|
|
2,280 |
39,157 |
|
38,500 |
|
|
|
|
2,290 |
39,258 |
|
38,600 |
|
|
|
|
2,300 |
39,356 |
|
38,800 |
|
|
|
|
2,310 |
39,452 |
|
|
|
|
|
|
2,320 |
39,547 |
|
|
|
|
|
|
2,330 |
39,639 |
|
|
|
|
|
|
2,340 |
39,729 |
|
|
|
|
|
|
2,350 |
39,817 |
|
|
|
|
|
|
2,360 |
39,903 |
|
|
|
|
|
|
2,370 |
39,986 |
|
|
|
|
|
|
2,380 |
40,068 |
|
|
|
|
|
|
2,390 |
40,146 |
|
|
|
|
|
|
2,400 |
40,223 |
|
|
|
|
|
|
2,410 |
40,297 |
|
|
|
|
|
|
2,420 |
40,368 |
|
|
|
|
|
|
2,430 |
40,437 |
|
|
|
|
|
|
2,440 |
40,503 |
|
|
|
|
|
|
2,450 |
40,566 |
|
|
|
|
|
|
2,460 |
40,627 |
|
|
|
|
|
|
2,470 |
40,685 |
|
|
|
|
|
|
2,480 |
40,740 |
|
|
|
|
|
|
2,490 |
40,792 |
|
|
|
|
|