Type A-1, A-2, A-3, AuPt, B, C
|
Values in µV |
Type A-1 |
Type A-2 |
Type A-3 |
Type AuPt |
Type B |
Type C |
|---|---|---|---|---|---|---|
|
[°C] |
0…490°C |
0…490°C |
0…490°C |
0…490°C |
200…490°C |
0…490°C |
|
0 |
0 |
0 |
0 |
0 |
|
0 |
|
10 |
122 |
118 |
119 |
62 |
|
135 |
|
20 |
246 |
241 |
241 |
128 |
|
272 |
|
30 |
374 |
367 |
366 |
198 |
|
412 |
|
40 |
504 |
497 |
494 |
271 |
|
554 |
|
50 |
637 |
630 |
625 |
348 |
|
698 |
|
60 |
772 |
766 |
759 |
428 |
|
845 |
|
70 |
910 |
905 |
896 |
511 |
|
993 |
|
80 |
1,050 |
1,047 |
1,034 |
597 |
|
1,144 |
|
90 |
1,193 |
1,191 |
1,176 |
686 |
|
1,296 |
|
100 |
1,337 |
1,338 |
1,319 |
778 |
|
1,451 |
|
110 |
1,483 |
1,487 |
1,464 |
873 |
|
1,607 |
|
120 |
1,632 |
1,637 |
1,611 |
971 |
|
1,765 |
|
130 |
1,782 |
1,790 |
1,760 |
1,071 |
|
1,925 |
|
140 |
1,933 |
1,945 |
1,910 |
1,174 |
|
2,087 |
|
150 |
2,086 |
2,101 |
2,062 |
1,280 |
|
2,250 |
|
160 |
2,241 |
2,258 |
2,216 |
1,388 |
|
2,415 |
|
170 |
2,397 |
2,417 |
2,371 |
1,499 |
|
2,581 |
|
180 |
2,554 |
2,578 |
2,527 |
1,612 |
|
2,749 |
|
190 |
2,712 |
2,739 |
2,684 |
1,727 |
|
2,918 |
|
200 |
2,872 |
2,902 |
2,842 |
1,845 |
178 |
3,089 |
|
210 |
3,032 |
3,065 |
3,002 |
1,965 |
199 |
3,261 |
|
220 |
3,194 |
3,230 |
3,162 |
2,087 |
220 |
3,434 |
|
230 |
3,356 |
3,395 |
3,323 |
2,212 |
243 |
3,609 |
|
240 |
3,519 |
3,561 |
3,485 |
2,339 |
267 |
3,785 |
|
250 |
3,683 |
3,728 |
3,648 |
2,467 |
291 |
3,962 |
|
260 |
3,848 |
3,896 |
3,811 |
2,598 |
317 |
4,140 |
|
270 |
4,013 |
4,064 |
3,975 |
2,731 |
344 |
4,319 |
|
280 |
4,179 |
4,232 |
4,139 |
2,866 |
372 |
4,500 |
|
290 |
4,346 |
4,401 |
4,304 |
3,003 |
401 |
4,681 |
|
300 |
4,513 |
4,571 |
4,470 |
3,142 |
431 |
4,863 |
|
310 |
4,681 |
4,741 |
4,636 |
3,283 |
462 |
5,047 |
|
320 |
4,849 |
4,911 |
4,802 |
3,425 |
494 |
5,231 |
|
330 |
5,017 |
5,081 |
4,969 |
3,570 |
527 |
5,416 |
|
340 |
5,186 |
5,252 |
5,136 |
3,716 |
561 |
5,601 |
|
350 |
5,355 |
5,423 |
5,303 |
3,865 |
596 |
5,788 |
|
360 |
5,524 |
5,594 |
5,471 |
4,015 |
632 |
5,975 |
|
370 |
5,694 |
5,766 |
5,638 |
4,167 |
669 |
6,163 |
|
380 |
5,864 |
5,937 |
5,806 |
4,321 |
707 |
6,352 |
|
390 |
6,034 |
6,109 |
5,974 |
4,476 |
746 |
6,541 |
|
400 |
6,204 |
6,280 |
6,143 |
4,633 |
787 |
6,731 |
|
410 |
6,374 |
6,452 |
6,311 |
4,793 |
828 |
6,921 |
|
420 |
6,544 |
6,624 |
6,479 |
4,953 |
870 |
7,112 |
|
430 |
6,715 |
6,796 |
6,648 |
5,116 |
913 |
7,304 |
|
440 |
6,885 |
6,967 |
6,816 |
5,280 |
957 |
7,496 |
|
450 |
7,056 |
7,139 |
6,985 |
5,446 |
1,002 |
7,688 |
|
460 |
7,226 |
7,311 |
7,153 |
5,614 |
1,048 |
7,881 |
|
470 |
7,397 |
7,483 |
7,322 |
5,783 |
1,095 |
8,074 |
|
480 |
7,568 |
7,654 |
7,490 |
5,954 |
1,143 |
8,267 |
|
490 |
7,738 |
7,826 |
7,659 |
6,127 |
1,192 |
8,461 |
Continuation type A-1, A-2, A-3, AuPt, B, C
|
Values in µV |
Type A-1 |
Type A-2 |
Type A-3 |
Type AuPt |
Type B |
Type C |
|---|---|---|---|---|---|---|
|
[°C] |
500…990°C |
500…990°C |
500…990°C |
500…990°C |
500…990°C |
500…990°C |
|
500 |
7,908 |
7,998 |
7,827 |
6,301 |
1,242 |
8,655 |
|
510 |
8,079 |
8,169 |
7,996 |
6,477 |
1,293 |
8,849 |
|
520 |
8,249 |
8,340 |
8,164 |
6,655 |
1,344 |
9,044 |
|
530 |
8,419 |
8,512 |
8,332 |
6,834 |
1,397 |
9,239 |
|
540 |
8,589 |
8,683 |
8,500 |
7,015 |
1,451 |
9,434 |
|
550 |
8,759 |
8,854 |
8,668 |
7,198 |
1,505 |
9,629 |
|
560 |
8,929 |
9,025 |
8,836 |
7,382 |
1,561 |
9,824 |
|
570 |
9,098 |
9,195 |
9,004 |
7,568 |
1,617 |
10,019 |
|
580 |
9,268 |
9,366 |
9,171 |
7,755 |
1,674 |
10,215 |
|
590 |
9,437 |
9,536 |
9,339 |
7,944 |
1,732 |
10,410 |
|
600 |
9,606 |
9,707 |
9,506 |
8,135 |
1,792 |
10,606 |
|
610 |
9,775 |
9,877 |
9,673 |
8,328 |
1,852 |
10,801 |
|
620 |
9,944 |
10,046 |
9,840 |
8,522 |
1,912 |
10,997 |
|
630 |
10,112 |
10,216 |
10,007 |
8,717 |
1,974 |
11,192 |
|
640 |
10,280 |
10,386 |
10,173 |
8,915 |
2,037 |
11,388 |
|
650 |
10,448 |
10,555 |
10,340 |
9,113 |
2,101 |
11,583 |
|
660 |
10,616 |
10,724 |
10,506 |
9,314 |
2,165 |
11,778 |
|
670 |
10,783 |
10,893 |
10,672 |
9,516 |
2,230 |
11,974 |
|
680 |
10,950 |
11,061 |
10,837 |
9,720 |
2,296 |
12,169 |
|
690 |
11,117 |
11,230 |
11,003 |
9,925 |
2,363 |
12,364 |
|
700 |
11,284 |
11,398 |
11,168 |
10,132 |
2,431 |
12,558 |
|
710 |
11,450 |
11,566 |
11,333 |
10,341 |
2,499 |
12,753 |
|
720 |
11,616 |
11,733 |
11,498 |
10,551 |
2,569 |
12,947 |
|
730 |
11,782 |
11,900 |
11,662 |
10,763 |
2,639 |
13,142 |
|
740 |
11,948 |
12,068 |
11,826 |
10,976 |
2,710 |
13,336 |
|
750 |
12,113 |
12,234 |
11,990 |
11,191 |
2,782 |
13,529 |
|
760 |
12,278 |
12,401 |
12,154 |
11,408 |
2,854 |
13,723 |
|
770 |
12,442 |
12,567 |
12,317 |
11,626 |
2,928 |
13,916 |
|
780 |
12,606 |
12,733 |
12,480 |
11,846 |
3,002 |
14,109 |
|
790 |
12,770 |
12,898 |
12,643 |
12,068 |
3,078 |
14,302 |
|
800 |
12,934 |
13,064 |
12,805 |
12,291 |
3,154 |
14,494 |
|
810 |
13,097 |
13,228 |
12,967 |
12,516 |
3,230 |
14,686 |
|
820 |
13,260 |
13,393 |
13,129 |
12,742 |
3,308 |
14,877 |
|
830 |
13,423 |
13,557 |
13,291 |
12,970 |
3,386 |
15,069 |
|
840 |
13,585 |
13,721 |
13,452 |
13,199 |
3,466 |
15,260 |
|
850 |
13,747 |
13,885 |
13,613 |
13,430 |
3,546 |
15,450 |
|
860 |
13,908 |
14,048 |
13,773 |
13,663 |
3,626 |
15,640 |
|
870 |
14,069 |
14,210 |
13,933 |
13,897 |
3,708 |
15,830 |
|
880 |
14,230 |
14,373 |
14,093 |
14,133 |
3,790 |
16,020 |
|
890 |
14,390 |
14,535 |
14,252 |
14,370 |
3,873 |
16,208 |
|
900 |
14,550 |
14,696 |
14,411 |
14,609 |
3,957 |
16,397 |
|
910 |
14,710 |
14,858 |
14,570 |
14,850 |
4,041 |
16,585 |
|
920 |
14,869 |
15,018 |
14,728 |
15,092 |
4,127 |
16,773 |
|
930 |
15,028 |
15,179 |
14,886 |
15,336 |
4,213 |
16,960 |
|
940 |
15,186 |
15,339 |
15,044 |
15,581 |
4,299 |
17,147 |
|
950 |
15,344 |
15,498 |
15,201 |
15,828 |
4,387 |
17,333 |
|
960 |
15,502 |
15,657 |
15,357 |
16,076 |
4,475 |
17,519 |
|
970 |
15,659 |
15,816 |
15,514 |
16,326 |
4,564 |
17,704 |
|
980 |
15,815 |
15,974 |
15,669 |
16,578 |
4,653 |
17,889 |
|
990 |
15,972 |
16,132 |
15,825 |
16,831 |
4,743 |
18,073 |
Continuation type A-1, A-2, A-3, AuPt, B, C
|
Values in µV |
Type A-1 |
Type A-2 |
Type A-3 |
Type AuPt |
Type B |
Type C |
|---|---|---|---|---|---|---|
|
[°C] |
1,000…1,490°C |
1,000…1,490°C |
1,000…1,490°C |
1,000°C |
1,000…1,490°C |
1,000…1,490°C |
|
1,000 |
16,128 |
16,289 |
15,980 |
17,085 |
4,834 |
18,257 |
|
1,010 |
16,283 |
16,446 |
16,134 |
|
4,926 |
18,440 |
|
1,020 |
16,438 |
16,602 |
16,288 |
|
5,018 |
18,623 |
|
1,030 |
16,593 |
16,758 |
16,442 |
|
5,111 |
18,805 |
|
1,040 |
16,747 |
16,913 |
16,595 |
|
5,205 |
18,987 |
|
1,050 |
16,901 |
17,068 |
16,748 |
|
5,299 |
19,168 |
|
1,060 |
17,054 |
17,222 |
16,900 |
|
5,394 |
19,349 |
|
1,070 |
17,207 |
17,376 |
17,052 |
|
5,489 |
19,529 |
|
1,080 |
17,359 |
17,530 |
17,203 |
|
5,585 |
19,709 |
|
1,090 |
17,511 |
17,683 |
17,354 |
|
5,682 |
19,888 |
|
1,100 |
17,662 |
17,835 |
17,505 |
|
5,780 |
20,066 |
|
1,110 |
17,813 |
17,987 |
17,654 |
|
5,878 |
20,244 |
|
1,120 |
17,964 |
18,138 |
17,804 |
|
5,976 |
20,421 |
|
1,130 |
18,114 |
18,289 |
17,953 |
|
6,075 |
20,598 |
|
1,140 |
18,263 |
18,439 |
18,101 |
|
6,175 |
20,774 |
|
1,150 |
18,412 |
18,589 |
18,249 |
|
6,276 |
20,950 |
|
1,160 |
18,561 |
18,738 |
18,396 |
|
6,377 |
21,125 |
|
1,170 |
18,709 |
18,887 |
18,543 |
|
6,478 |
21,299 |
|
1,180 |
18,857 |
19,035 |
18,690 |
|
6,580 |
21,473 |
|
1,190 |
19,004 |
19,183 |
18,836 |
|
6,683 |
21,647 |
|
1,200 |
19,150 |
19,330 |
18,981 |
|
6,786 |
21,819 |
|
1,210 |
19,297 |
19,477 |
19,126 |
|
6,890 |
21,991 |
|
1,220 |
19,442 |
19,623 |
19,270 |
|
6,995 |
22,163 |
|
1,230 |
19,587 |
19,769 |
19,414 |
|
7,100 |
22,334 |
|
1,240 |
19,732 |
19,914 |
19,557 |
|
7,205 |
22,504 |
|
1,250 |
19,876 |
20,059 |
19,700 |
|
7,311 |
22,674 |
|
1,260 |
20,020 |
20,203 |
19,843 |
|
7,417 |
22,843 |
|
1,270 |
20,163 |
20,347 |
19,984 |
|
7,524 |
23,012 |
|
1,280 |
20,305 |
20,490 |
20,126 |
|
7,632 |
23,180 |
|
1,290 |
20,448 |
20,632 |
20,266 |
|
7,740 |
23,347 |
|
1,300 |
20,589 |
20,774 |
20,407 |
|
7,848 |
23,514 |
|
1,310 |
20,730 |
20,916 |
20,546 |
|
7,957 |
23,680 |
|
1,320 |
20,871 |
21,057 |
20,686 |
|
8,066 |
23,846 |
|
1,330 |
21,011 |
21,198 |
20,824 |
|
8,176 |
24,010 |
|
1,340 |
21,150 |
21,338 |
20,963 |
|
8,286 |
24,175 |
|
1,350 |
21,289 |
21,478 |
21,100 |
|
8,397 |
24,339 |
|
1,360 |
21,428 |
21,617 |
21,237 |
|
8,508 |
24,502 |
|
1,370 |
21,566 |
21,755 |
21,374 |
|
8,620 |
24,664 |
|
1,380 |
21,703 |
21,894 |
21,510 |
|
8,731 |
24,826 |
|
1,390 |
21,840 |
22,031 |
21,646 |
|
8,844 |
24,988 |
|
1,400 |
21,976 |
22,168 |
21,781 |
|
8,956 |
25,148 |
|
1,410 |
22,112 |
22,305 |
21,916 |
|
9,069 |
25,308 |
|
1,420 |
22,248 |
22,441 |
22,050 |
|
9,182 |
25,468 |
|
1,430 |
22,382 |
22,577 |
22,184 |
|
9,296 |
25,627 |
|
1,440 |
22,517 |
22,713 |
22,317 |
|
9,410 |
25,785 |
|
1,450 |
22,650 |
22,847 |
22,450 |
|
9,524 |
25,943 |
|
1,460 |
22,784 |
22,982 |
22,582 |
|
9,639 |
26,100 |
|
1,470 |
22,916 |
23,116 |
22,714 |
|
9,753 |
26,256 |
|
1,480 |
23,048 |
23,249 |
22,845 |
|
9,868 |
26,412 |
|
1,490 |
23,180 |
23,382 |
22,976 |
|
9,984 |
26,568 |
Continuation type A-1, A-2, A-3, B, C
|
values in µV |
type A-1 |
type A-2 |
type A-3 |
|
type B |
type C |
|---|---|---|---|---|---|---|
|
[°C] |
1,500…1,990°C |
1,500…1,800°C |
1,500…1,800°C |
|
1,500…1,820°C |
1,500…1,990°C |
|
1,500 |
23,311 |
23,515 |
23,106 |
|
10,099 |
26,722 |
|
1,510 |
23,442 |
23,647 |
23,236 |
|
10,215 |
26,876 |
|
1,520 |
23,572 |
23,778 |
23,365 |
|
10,331 |
27,030 |
|
1,530 |
23,701 |
23,910 |
23,494 |
|
10,447 |
27,183 |
|
1,540 |
23,830 |
24,040 |
23,622 |
|
10,563 |
27,335 |
|
1,550 |
23,959 |
24,170 |
23,750 |
|
10,679 |
27,486 |
|
1,560 |
24,087 |
24,300 |
23,878 |
|
10,796 |
27,637 |
|
1,570 |
24,214 |
24,429 |
24,005 |
|
10,913 |
27,788 |
|
1,580 |
24,341 |
24,558 |
24,131 |
|
11,029 |
27,938 |
|
1,590 |
24,467 |
24,686 |
24,257 |
|
11,146 |
28,087 |
|
1,600 |
24,593 |
24,814 |
24,382 |
|
11,263 |
28,236 |
|
1,610 |
24,718 |
24,941 |
24,507 |
|
11,380 |
28,384 |
|
1,620 |
24,843 |
25,067 |
24,632 |
|
11,497 |
28,531 |
|
1,630 |
24,967 |
25,193 |
24,756 |
|
11,614 |
28,678 |
|
1,640 |
25,091 |
25,319 |
24,879 |
|
11,731 |
28,824 |
|
1,650 |
25,214 |
25,444 |
25,002 |
|
11,848 |
28,969 |
|
1,660 |
25,337 |
25,568 |
25,124 |
|
11,965 |
29,114 |
|
1,670 |
25,459 |
25,692 |
25,246 |
|
12,082 |
29,259 |
|
1,680 |
25,580 |
25,815 |
25,367 |
|
12,199 |
29,402 |
|
1,690 |
25,701 |
25,937 |
25,488 |
|
12,316 |
29,546 |
|
1,700 |
25,822 |
26,059 |
25,608 |
|
12,433 |
29,688 |
|
1,710 |
25,942 |
26,180 |
25,728 |
|
12,549 |
29,830 |
|
1,720 |
26,061 |
26,300 |
25,847 |
|
12,666 |
29,971 |
|
1,730 |
26,180 |
26,419 |
25,965 |
|
12,782 |
30,112 |
|
1,740 |
26,299 |
26,538 |
26,083 |
|
12,898 |
30,252 |
|
1,750 |
26,416 |
26,656 |
26,200 |
|
13,014 |
30,391 |
|
1,760 |
26,534 |
26,773 |
26,316 |
|
13,130 |
30,530 |
|
1,770 |
26,650 |
26,889 |
26,431 |
|
13,246 |
30,668 |
|
1,780 |
26,767 |
27,004 |
26,546 |
|
13,361 |
30,805 |
|
1,790 |
26,882 |
27,118 |
26,660 |
|
13,476 |
30,942 |
|
1,800 |
26,998 |
27,232 |
26,773 |
|
13,591 |
31,078 |
|
1,810 |
27,112 |
|
|
|
13,706 |
31,214 |
|
1,820 |
27,226 |
|
|
|
13,820 |
31,349 |
|
1,830 |
27,340 |
|
|
|
|
31,483 |
|
1,840 |
27,453 |
|
|
|
|
31,617 |
|
1,850 |
27,565 |
|
|
|
|
31,749 |
|
1,860 |
27,677 |
|
|
|
|
31,882 |
|
1,870 |
27,789 |
|
|
|
|
32,013 |
|
1,880 |
27,900 |
|
|
|
|
32,144 |
|
1,890 |
28,010 |
|
|
|
|
32,274 |
|
1,900 |
28,120 |
|
|
|
|
32,404 |
|
1,910 |
28,229 |
|
|
|
|
32,533 |
|
1,920 |
28,337 |
|
|
|
|
32,661 |
|
1,930 |
28,445 |
|
|
|
|
32,788 |
|
1,940 |
28,553 |
|
|
|
|
32,915 |
|
1,950 |
28,660 |
|
|
|
|
33,041 |
|
1,960 |
28,766 |
|
|
|
|
33,166 |
|
1,970 |
28,872 |
|
|
|
|
33,291 |
|
1,980 |
28,977 |
|
|
|
|
33,415 |
|
1,990 |
29,082 |
|
|
|
|
33,538 |
Continuation type A-1, type C
|
Values in µV |
Type A-1 |
|
|
|
|
Type C |
|---|---|---|---|---|---|---|
|
[°C] |
2,000…2,500°C |
|
|
|
|
2,000…2,320°C |
|
2,000 |
29,186 |
|
|
|
|
33,660 |
|
2,010 |
29,290 |
|
|
|
|
33,782 |
|
2,020 |
29,392 |
|
|
|
|
33,902 |
|
2,030 |
29,495 |
|
|
|
|
34,022 |
|
2,040 |
29,597 |
|
|
|
|
34,142 |
|
2,050 |
29,698 |
|
|
|
|
34,260 |
|
2,060 |
29,798 |
|
|
|
|
34,378 |
|
2,070 |
29,898 |
|
|
|
|
34,494 |
|
2,080 |
29,998 |
|
|
|
|
34,610 |
|
2,090 |
30,096 |
|
|
|
|
34,725 |
|
2,100 |
30,194 |
|
|
|
|
34,839 |
|
2,110 |
30,292 |
|
|
|
|
34,953 |
|
2,120 |
30,389 |
|
|
|
|
35,065 |
|
2,130 |
30,485 |
|
|
|
|
35,177 |
|
2,140 |
30,581 |
|
|
|
|
35,288 |
|
2,150 |
30,676 |
|
|
|
|
35,397 |
|
2,160 |
30,770 |
|
|
|
|
35,506 |
|
2,170 |
30,864 |
|
|
|
|
35,614 |
|
2,180 |
30,957 |
|
|
|
|
35,721 |
|
2,190 |
31,050 |
|
|
|
|
35,827 |
|
2,200 |
31,142 |
|
|
|
|
35,932 |
|
2,210 |
31,233 |
|
|
|
|
36,036 |
|
2,220 |
31,324 |
|
|
|
|
36,138 |
|
2,230 |
31,414 |
|
|
|
|
36,240 |
|
2,240 |
31,504 |
|
|
|
|
36,341 |
|
2,250 |
31,593 |
|
|
|
|
36,441 |
|
2,260 |
31,681 |
|
|
|
|
36,539 |
|
2,270 |
31,769 |
|
|
|
|
36,637 |
|
2,280 |
31,856 |
|
|
|
|
36,733 |
|
2,290 |
31,942 |
|
|
|
|
36,828 |
|
2,300 |
32,028 |
|
|
|
|
36,922 |
|
2,310 |
32,113 |
|
|
|
|
37,015 |
|
2,320 |
32,198 |
|
|
|
|
37,107 |
|
2,330 |
32,282 |
|
|
|
|
|
|
2,340 |
32,365 |
|
|
|
|
|
|
2,350 |
32,448 |
|
|
|
|
|
|
2,360 |
32,531 |
|
|
|
|
|
|
2,370 |
32,613 |
|
|
|
|
|
|
2,380 |
32,694 |
|
|
|
|
|
|
2,390 |
32,775 |
|
|
|
|
|
|
2,400 |
32,856 |
|
|
|
|
|
|
2,410 |
32,936 |
|
|
|
|
|
|
2,420 |
33,015 |
|
|
|
|
|
|
2,430 |
33,095 |
|
|
|
|
|
|
2,440 |
33,173 |
|
|
|
|
|
|
2,450 |
33,252 |
|
|
|
|
|
|
2,460 |
33,330 |
|
|
|
|
|
|
2,470 |
33,408 |
|
|
|
|
|
|
2,480 |
33,485 |
|
|
|
|
|
|
2,490 |
33,563 |
|
|
|
|
|
|
2,500 |
33,640 |
|
|
|
|
|