Overview of common resistance sensors

The following overview shows some common resistance sensors which are suitable for temperature measurement. See also the following chapter.

Type

Temperature measuring range

Resistance range [Ω], approx.

Temperature coefficient
[Ω/K], @ approx. 100 °C

Material /
element type

Nominal resistance

 

Pt100

-200 … 850 °C

~18 Ω … ~390 Ω

0.38 Ω/K

Platinum

100 Ω (T = 0 °C)

Pt200

~30 Ω  … . ~750 Ω

0.76 Ω/K

200 Ω (T = 0 °C)

Pt500

~90 Ω  … . ~1850 Ω

1.9 Ω/K

500 Ω (T = 0 °C)

Pt1000

~185 Ω  … . ~3800 Ω

3.8 Ω/K

1000 Ω (T = 0 °C)

Ni100

-60 … 250 °C

~70 Ω … ~230 Ω

0.7 Ω/K

Nickel

100 Ω (T = 0 °C)

Ni120

~65 Ω … ~380 Ω

0.9 Ω/K

120 Ω (T = 0 °C)

Ni1000

~700 Ω … ~2000 Ω

7 Ω/K

1000 Ω (T = 0 °C)

Ni1000TK5000

~700 Ω … ~2000 Ω

5.6 Ω/K

1000 Ω (T = 0 °C)

1500 Ω (T = 100 °C)

KT100/110/130/210/230

KTY10/11/13/16/19

KTY81/82-110,120,150

KTY81-121

KTY81-122

KTY81-151

KTY81-151

KTY81/82-210,220,250

KTY81-221

KTY81-222

KTY81-251

KTY81-252

-55 … 150 °C

~500 … ~2200 Ω

Temperature-dependent and to be obtained from the sensor
manufacturer

Silicon

~2000 Ω (T = 25 °C)

~1000 Ω (T = 25 °C)

KTY83-110,120,150

KTY83-121

KTY83-122

KTY83-151

KTY83-152

-55 … 175 °C

~500 … ~2500 Ω

Silicon

~1000 Ω (T = 25 °C)

KTY84-130,150

KTY84-151

-40 … 300 °C

~350 … ~2500 Ω

Silicon

~1000 Ω (T = 100 °C)

KTY21/23-6

KTY1x-5

KTY1x-7

KTY21/23-5

KTY21/23-7

-55 … 150 °C

~500 … ~4000 Ω

Silicon

~1000 Ω (T = 25 °C)

Type

Temperature measuring range

Resistance range [Ω], approx.

Temperature coefficient
[Ω/K]

Material /
element type

Nominal resistance

NTC2K2 2)

-55 … 150 °C 1)

~75 Ω … 150 kΩ

@-40 … +10 °C: 1200 Ω/K

@+10 … +30 °C: 110 Ω/K

@+30 … 130 °C: 16 Ω/K

Different Semiconductors

2200 Ω (T = 25 °C)

NTC3K 2)

~100 Ω … 205 kΩ

@-40 … +10 °C: 1600 Ω/K

@+10 … +30 °C: 140 Ω/K

@+30 … 130 °C: 41 Ω/K

3000 Ω (T = 25 °C)

NTC5K 2)

~150 Ω … 330 kΩ

@-40 … +10 °C: 2600 Ω/K

@+10 … +30 °C: 240 Ω/K

@+30 … 130 °C: 68 Ω/K

5000 Ω (T = 25 °C)

NTC10K 2) 3)

~300 Ω  … 690 kΩ

@-40 … +10 °C: 5500 Ω/K

@+10 … +30 °C: 470 Ω/K

@+30 … 130 °C: 71 Ω/K

10000 Ω (T = 25 °C)

NTC20K 2) 3)

~500 Ω  … 1.2 MΩ

@-40 … +10 °C: 10 kΩ/K

@+10 … +30 °C: 930 Ω/K

@+30 … 130 °C: 140 Ω/K

20000 Ω (T = 25 °C)

NTC100K 2)

~3 kΩ  … 3.3 MΩ

@-40 … +10 °C: 32 kΩ/K

@+10 … +30 °C: 4.7 kΩ/K

@+30 … 130 °C: 700 Ω/K

 

1) The values may vary depending on the sensor manufacturer and the intended application.

2) The temperature coefficient of the NTC is extremely temperature-dependent, the values given are only orientation values!

3) Other variants of this type also exist, which differ in the characteristic values!

This informative diagram shows that an extremely wide resistance range is covered, especially with NTC sensors:

Overview of common resistance sensors 1: