Start-up procedure and Diagnostics LEDs

Start-up procedure and Diagnostic

After switching on, the ILxxxx-B520 immediately checks the connected configuration. Error-free start-up is signalled by the red "I/O ERR“ LED being extinguished. If the “I/O ERR” LED blinks, an error in the area of the extension boxes is indicated. The error code can be determined from the frequency and number of blinks. This permits rapid rectification of the error. There is a detailed description in the section on "The diagnostic LEDs".

The diagnostic LEDs

The ILxxxx-B520 has two groups of LEDs for the display of status. The upper group with two LEDs indicates the status of the respective fieldbus. The significance of the “fieldbus status“ LED is explained in the relevant sections of this manual - it conforms to conventional fieldbus displays.

On the bottom of the ILxxxx-B520 are two more green LEDs that indicate the supply voltage. The left hand LED indicates the presence of the 24 V supply for the ILxxxx-B520. The right hand LED indicates the presence of the supply to the power contacts.

Local errors

Two LEDs, the “I/O LEDs”, in the area below the field bus status LEDs referred to above, serve to indicate the operating status of the ILxxxx-B520 and the connected extension boxes. The green LED lights up in order to indicate fault-free operation. The red LED blinks with two different frequencies in order to indicate an error. The error is encoded in the blinks as follows:

Blink code

Fast blinking

Start of the error code

First slow sequence

Error code

Second slow sequence

Error code argument

Error location

Error code

Error code argument

Description

1 pulse

0

1

2

EEPROM checksum error

Inline code buffer overflow

Unknown data type

2 pulses

 

0

n (n > 0)

Programmed configuration

Incorrect table entry / Ilxxxx-B520

Incorrect table comparison (extension box n)

3 pulses

0

n

Interruption of IP-Link bus

Break behind extension box (0: ILxxxx-B520)

4 pulses

0

n

IP-Link bus data error (incorrect telegram)

Extension box n (0: Ilxxxx-B520)

5 pulses

n

IP-Link bus error in register communication with extension box n

6 pulses

0

n (n > 0)

Special fieldbus error

11 pulses

n

IR Error, no communication, extension box n is not processing the IR commands

12 pulses

n

More than 120 extension boxes

n extension boxes too much

13 pulses

n

unknown box type, extension box n

The number of pulses in the first sequence indicates the error type, while the second sequence indicates the position of the last extension box before the fault.

In the case of some errors, rectification does not cause the ILxxxx-B520 to leave the blink sequence. The ILxxxx-B520 stays in the "Stop" state. The ILxxxx-B520 can only be re-started either by switching the power supply off and on again, or by a scanner reset.