Digital Output Channel Object
The ILxxxx-B520 provides Digital Output Channel Objects to access the digital output channels data of the ILxxxx-B520 and the connected extension boxes. For each digital output channel exits one instance of the Digital Output Channel Object Class.
The Digital Output Channel Object Class is Vendor specific and within in the range of the Vendor specific Class Codes.
Class Code: 102 (66hex)
Class Attributes
Attribute ID | Access rule | Name | Data type | Description | Semantics of Value |
|---|---|---|---|---|---|
1 | get | Revision | UINT | Revision of implementation | 1 |
2 | get | Max. Instance | UINT | Max. number of instances |
|
Instance Attributes
Attribute ID | Access rule | Name | Data type | Description | Semantics of Value |
|---|---|---|---|---|---|
1 (01hex) | Get/Set | Value | BOOL | Output Channel Value | 0: OFF |
Common Services
Service Code | Service Name | Description |
|---|---|---|
14 (0Ehex) | Get_Attribute_Single | Returns the contents of the specified attribute |
16 (10hex) | Set_Attribute_Single | Modifies an attribute Value |