IL Config Object
The ILxxxx-B520 provides the vendor specific object class to access its status, diagnostic and configuration data. Within the IL Config Object the full range of Registers and Status-Information of the ILxxxx-B520 and the connected extension boxes is available.
The IL Config Object Class is Vendor specific and within in the Range of the Vendor specific Class Codes.
Class Code: 100 (64hex)
Class Attributes
Attribute ID | Access rule | Name | Data type | Description | Semantics of Value |
|---|---|---|---|---|---|
1 | Get | Revision | UINT | Revision of implementation | 1 |
2 | Get | Max. Instance | UINT | Max. number of instances | 1 |
Instance Attributes
Attribute ID | Access rule | Name | Data type | Description | Semantics of Value |
|---|---|---|---|---|---|
1 | Get/Set | Terminal | USINT | Number of terminal | 0: Coupler >0: Channels |
2 | Get/Set | Table Number | USINT | Number of table | See ILxxxx-B520 /Channel Description |
3 | Get/Set | Register Number | USINT | Number of Register | See ILxxxx-B520 /Channel Description |
4 | Get/Set | Register Data | DWORD | Register Value | see semantics |
5 | Get | IL-Status | BYTE | Status of the ILxxxx-B520 | see semantics |
6 | Get | Extension Box-Diagnosis | WORD | Diagnosis of the extension boxes | see semantics |
10 | Get/Set | IO Error Action | BYTE | Action to be performed if a fieldbus error occurs | see semantics |
11 | Get/Set | Poll produced data type | BYTE | Type of IO data produced via the Poll mode | see semantics |
12 | Get/Set | COS/ Cyclic produced data type | BYTE | Type of IO data produced via the Change of State / Cyclic mode | see semantics |
13 | Get/Set | Bit Strobe produced data type | BYTE | Type of IO data produced via the Bit Strobe / Cyclic mode | see semantics |
14 | Get/Set | Poll / COS/ Cyclic consumed data type | BYTE | Type of IO data consumed via the Poll / Change of State / Cyclic mode | see semantics |
Instance Attributes
Attribute ID | Access rule | Name | Data type | Description | Semantics of Value |
|---|---|---|---|---|---|
15 | Get | Input Size Poll Mode | BYTE | Number of Bytes produced via the Poll mode |
|
16 | Get | Input Size Bit Strobe Mode | BYTE | Number of Bytes produced via the Bit Strobe mode |
|
17 | Get | Input Size COS / Cyclic Mode | BYTE | Number of Bytes produced via the Change of State / Cyclic mode |
|
18 | Get | Output Size Poll / COS/ Cyclic Mode | BYTE | Number of Bytes consumed via the Poll / Change of State /Cyclic mode |
|
19 | Get/Set | Device Diagnostics | BYTE | Enables Diagnosis of complex (analog/special-function) extension boxes | see semantics |
20 | Get | Analog Out Length | BYTE | Size of analog output data in bits |
|
21 | Get | Analog In Length | BYTE | Size of analog input data in bits |
|
22 | Get | Digital In Length | BYTE | Size of digital output data in bits |
|
23 | Get | Digital Out Length | BYTE | Size of digital input data in Bits |
|
25 | Get/Set | Bus Off | BYTE | Behavior of ILxxxx-B520 after detection of a Bus-Off event | see semantics |