IL Config Object
The ILxxxx-B520 provides the vendor specific object class to access its status, diagnostic and configuration data. Within the IL Config Object the full range of Registers and Status-Information of the ILxxxx-B520 and the connected extension boxes is available.
The IL Config Object Class is Vendor specific and within in the Range of the Vendor specific Class Codes.
Class Code: 100 (64hex)
Class Attributes
| Attribute ID | Access rule | Name | Data type | Description | Semantics of Value | 
|---|---|---|---|---|---|
| 1 | Get | Revision | UINT | Revision of implementation | 1 | 
| 2 | Get | Max. Instance | UINT | Max. number of instances | 1 | 
Instance Attributes
| Attribute ID | Access rule | Name | Data type | Description | Semantics of Value | 
|---|---|---|---|---|---|
| 1 | Get/Set | Terminal | USINT | Number of terminal | 0: Coupler >0: Channels | 
| 2 | Get/Set | Table Number | USINT | Number of table | See ILxxxx-B520 /Channel Description | 
| 3 | Get/Set | Register Number | USINT | Number of Register | See ILxxxx-B520 /Channel Description | 
| 4 | Get/Set | Register Data | DWORD | Register Value | see semantics | 
| 5 | Get | IL-Status | BYTE | Status of the ILxxxx-B520 | see semantics | 
| 6 | Get | Extension Box-Diagnosis | WORD | Diagnosis of the extension boxes | see semantics | 
| 10 | Get/Set | IO Error Action | BYTE | Action to be performed if a fieldbus error occurs | see semantics | 
| 11 | Get/Set | Poll produced data type | BYTE | Type of IO data produced via the Poll mode | see semantics | 
| 12 | Get/Set | COS/ Cyclic produced data type | BYTE | Type of IO data produced via the Change of State / Cyclic mode | see semantics | 
| 13 | Get/Set | Bit Strobe produced data type | BYTE | Type of IO data produced via the Bit Strobe / Cyclic mode | see semantics | 
| 14 | Get/Set | Poll / COS/ Cyclic consumed data type | BYTE | Type of IO data consumed via the Poll / Change of State / Cyclic mode | see semantics | 
Instance Attributes
| Attribute ID | Access rule | Name | Data type | Description | Semantics of Value | 
|---|---|---|---|---|---|
| 15 | Get | Input Size Poll Mode | BYTE | Number of Bytes produced via the Poll mode | 
 | 
| 16 | Get | Input Size Bit Strobe Mode | BYTE | Number of Bytes produced via the Bit Strobe mode | 
 | 
| 17 | Get | Input Size COS / Cyclic Mode | BYTE | Number of Bytes produced via the Change of State / Cyclic mode | 
 | 
| 18 | Get | Output Size Poll / COS/ Cyclic Mode | BYTE | Number of Bytes consumed via the Poll / Change of State /Cyclic mode | 
 | 
| 19 | Get/Set | Device Diagnostics | BYTE | Enables Diagnosis of complex (analog/special-function) extension boxes | see semantics | 
| 20 | Get | Analog Out Length | BYTE | Size of analog output data in bits | 
 | 
| 21 | Get | Analog In Length | BYTE | Size of analog input data in bits | 
 | 
| 22 | Get | Digital In Length | BYTE | Size of digital output data in bits | 
 | 
| 23 | Get | Digital Out Length | BYTE | Size of digital input data in Bits | 
 | 
| 25 | Get/Set | Bus Off | BYTE | Behavior of ILxxxx-B520 after detection of a Bus-Off event | see semantics |