FC510x - PCI Cards for CANopen

ADS error codes

 

The ADS error codes have the following meaning:

 
Error
Description
0x1001
Insufficient memory for AMS command
0x1101
Incorrect data length at StartFieldbus
0x1102
Incorrect DeviceState at StartFieldbus
0x1103
Device cannot change from INIT to RUN
0x1104
Incorrect AdsState in INIT state
0x1105
Incorrect DeviceState at StopFieldbus
0x1106
Device cannot change from STOP to RUN if a CDL is not defined
0x1107
Device cannot change from STOP to RUN if a box is not defined
0x1108
Incorrect data length at StartDataTransfer
0x1109
Incorrect DeviceState at StartDataTransfer
0x110A
Incorrect AdsState in STOP state
0x110B
Device cannot change from RUN to INIT
0x110C
Incorrect data length at StopDataTransfer
0x110D
Incorrect DeviceState at StopDataTransfer
0x1110
Incorrect AdsState in RUN state
0x1111
Loading the device parameters is only permitted in the INIT state
0x1112
Incorrect data length at SetDeviceState
0x1113
AddBox not allowed in INIT state
0x1114
Incorrect data length at AddBox
0x1115
DeleteBox not allowed in INIT state
0x1116
Incorrect IndexOffset at DeleteBox
0x1117
Incorrect data length at DeleteBox
0x1118
ReadBox only with AdsRead
0x1119
AddCdl not allowed in INIT state
0x111A
Incorrect data length at AddCdl
0x111B
DeleteCdl not allowed in INIT state
0x111C
Incorrect IndexOffset at DeleteCdl
0x111D
Incorrect data length at DeleteCdl
0x111E
Incorrect IndexGroup at AdsWrite
0x111F
Device parameters cannot be read
Error
Description
0x1120
Box parameters cannot be read
0x1121
Cdl parameters cannot be read
0x1122
DeleteBox or DeleteCdl only with AdsWrite
0x1123
ReadBox only possible in STOP state
0x1124
Incorrect IndexOffset at ReadBox
0x1125
Incorrect data length at ReadBox
0x1126
Incorrect IndexGroup at AdsRead
0x1127
AddDeviceNotification not allowed in INIT state
0x1128
DelDeviceNotification not allowed in INIT state
0x1129
IndexOffset too large during reading of the device diagnostic data
0x112B
IndexOffset too large during reading of the box diagnostic data
0x112F
Insufficient memory for ReadBox response
0x113E
FC card is in a status in which the status state cannot be changed
0x1201
AddCdl: CDL no. is too large
0x1202
DeleteCdl only possible when CDL is stopped
0x1203
DeleteCdl not possible as no CDL defined
0x1204
Cycle could not be completed within the internal watchdog time
0x1301
AddCdl: I/O access multiplier is too large
0x1302
AddCdl: Start cycle must be smaller than I/O access multiplier
0x1303
AddCdl: Incorrect data length for output area
0x1304
AddCdl: Incorrect data offset for output area
0x1305
AddCdl: Output area is already defined
0x1306
AddCdl: Incorrect data length for input area
0x1307
AddCdl: Incorrect data offset for input area
0x1308
AddCdl: Input area is already defined
0x1309
AddCdl: Incorrect area type
0x130A
AddCdl: BoxNo has not been defined with AddBox
0x130B
AddCdl: Incorrect action type
0x130C
AddCdl: Insufficient memory for poll list
0x130D
AddCdl: Insufficient memory for poll list array
0x130E
AddCdl: Insufficient memory for actions
0x130F
AddCdl: CdlNo already exists
0x1310
DeleteCdl: CDL is not stopped
0x1311
AddCdl: Insufficient memory for asynchronous transmit list
0x1312
AddCdl: Insufficient memory for synchronous receive list
0x1313
AddCdl: Insufficient memory for asynchronous receive list
0x1316
AddCdl: Insufficient memory for synchronous receive list
0x1318
AddCdl: Only slave action allowed
0x1319
AddCdl: Insufficient memory for slave list
Error
Description
0x1601
AddBox: BoxNo is too large
0x1602
AddBox: Insufficient memory for ADS StartUp telegram
0x1604
DeleteBox: Box is not stopped
0x1605
AddBox: Insufficient memory for CDL telegram
0x1606
AddBox: Number of CDL telegrams is too large
0x1607
BoxRestart: Box is not stopped
0x1608
BoxRestart: AdsWriteControl syntax error
0x1609
BoxRestart: Incorrect AdsState
0x160A
Syntax error in AdsWrite to box port
0x160B
AMS CmdId is not supported by box port
0x160E
AdsReadState is not supported by box port
0x160F
AddBox: Insufficient memory for the ADS interface
0x1610
AddBox: AMS channel is invalid
0x1611
Error communicating with an AMS box
0x1613
Error communicating with an AMS box: Incorrect offset
0x1614
Error communicating with an AMS box: Data packet is too large
0x1615
Error communicating with an AMS box: AMS command is too large
0x1616
Error communicating with an AMS box: First data packet is too large
0x1617
Error communicating with an AMS box: First offset is incorrect
0x1701
AddDeviceNotification: Length of device diagnostic data to small
0x1702
AddDeviceNotification: Length of device diagnostic data to large
0x1703
AddDeviceNotification: Length of box diagnostic data to small
0x1704
AddDeviceNotification: Length of box diagnostic data to large
0x1705
AddDeviceNotification: Box is not defined
0x1706
AddDeviceNotification: Incorrect IndexGroup
0x1707
AddDeviceNotification: No more resources for client
0x1708
DelDeviceNotification: Incorrect handle
0x1801
StartFieldbus: In equidistant operation, shift time + safety time + 2*PLL sync. time must be greater than the cycle time
0x1802
StartFieldbus: Cycle time is too large
0x1803
StartFieldbus: Cycle time is too large
0x1804
StartFieldbus: Shift time is too large
0x1805
StartFieldbus: PLL sync time is too large
0x1806
StartFieldbus: Safety time is too large
0x1807
StartFieldbus: Cycle times shorter than 1 ms must be integral divisors of 1 ms
Error
Description
0x1A01
Memory could not be allocated from the huge heap, because it is larger than 0x8000 bytes
0x1A02
Memory could not be allocated from the near heap, because it is larger than 0x1000 bytes
0x1A03
Memory could not be allocated from the huge heap, because it is 0 byte
0x1A04
Memory could not be allocated from the near heap, because it is 0 byte
0x2001
StartFieldbus: Initialization of the CAN controller failed
0x2002
AddBox: Incorrect box parameter length
0x2003
AddBox: Incorrect box number
0x2004
AddBox: Syntax error in ADS StartUp parameters
0x2005
AddBox: Syntax errors in PDO parameters
0x2006
AddBox: Syntax error in data length
0x2007
AddBox: Insufficient memory
0x2008
AddCdl: Incorrect receive data length
0x2009
AddCdl: Incorrect transmit data length
0x200A
AddCdl: PDO is not defined
0x200B
AddCdl: PDO Id is already defined
0x200C
AddBox: Syntax error in ADS StartUp parameters
0x200D
AddBox: Syntax error in ADS StartUp parameters
0x200E
AddBox: Emergency Id is already defined
0x200F
AddBox: Too many PDOs defined
0x2010
AddCdl: Incorrect telegram index
0x2011
AddBox: Too many Rx or Tx PDOs
0x2012
AdsRead: Incorrect IndexGroup
0x2013
AdsRead: Incorrect IndexOffset
0x2014
AdsRead: Incorrect length
0x2015
AdsWrite: Incorrect IndexGroup
0x2016
AdsWrite: Incorrect IndexOffset
0x2017
AdsWrite: Incorrect length
0x2018
AddBox: Guarding time smaller than 10 is not possible
0x2019
AddBox: Incorrect transmission type in CAN Layer 2 node
0x201A
AdsRead: not possible at CAN Layer 2 node
0x201B
AdsWrite: not possible at CAN Layer 2 node
0x201C
AddBox: BootUp Id is already defined
0x201D
AddBox: BoxNo 0 is not possible
0x201E
StartFieldbus: Loading the device parameters is only possible in the OFFLINE state
0x201F
StartDataTransfer: No memory for copy queue
0x2020
ReadBox: no more memory
0x2021
ReadBox: SDO error or timeout
0x2022
ReadBox: SDO cannot be initialized
0x2023
StartFieldbus: reserved device parameter not equal to 0
Error
Description
0x2101
Insufficient memory for low-priority queues
0x2102
Insufficient memory for low-priority queues
0x2103
Insufficient memory at node boot-up
0x2104
Insufficient memory at node boot-up
0x2105
Insufficient memory at node boot-up
0x2106
Insufficient memory at node boot-up
0x2107
Insufficient memory at node boot-up
0x2108
Insufficient memory at node boot-up
0x2109
Insufficient memory at node boot-up
0x210A
Insufficient memory at node boot-up
0x210B
Insufficient memory at node boot-up
0x210C
Insufficient memory at node boot-up
0x210D
Insufficient memory at node boot-up
0x210E
Insufficient memory at node boot-up
0x210F
Insufficient memory at node boot-up
0x2110
Insufficient memory at node boot-up
0x2111
Insufficient memory at node boot-up
0x2112
Insufficient memory at node boot-up
0x2113
Insufficient memory at node boot-up
0x2114
Insufficient memory at node boot-up
0x2301
Insufficient memory for low-priority queues
0x2302
Insufficient memory for low-priority queues