FC510x - PCI cards for CANopen

LEDs

 
 FC5102Blende
FC510x - LEDs
 

LED behavior

The main card states can be quickly diagnosed by means of the red Error LED and the green Run LED:

Error LED (red)
Run LED (green)
Meaning
off
off
TwinCAT is stopped
off
on
All configured bus devices are error-free (box state = 0); TwinCAT task or process is running.
off
flashes at 2 Hz
The task whose process data are linked to the card is not running.
All configured bus devices found and error-free (box state = 0)
flashes at 2 Hz
on
At least one box state is not zero (e.g. device not found, wrong configuration, device fault), TwinCAT task is running
flashes at 2 Hz
off
At least one box state is not zero (e.g. device not found, wrong configuration, device fault), TwinCAT task is not running.
on
off
TwinCAT is running, CAN controller is Bus OFF. Physical CAN problem. Possible causes: e.g. missing termination resistor, bus line too long, wrong baud rate, node address assigned twice, wiring fault, short circuit.
Restart required
flashes at 20 Hz
flashes at 20 Hz
Configuration upload being carried out
flashes at 20 Hz
off
Card is in STOP mode