Parameterizing via Rotary Switches

By using the rotary switches, the following parameterizations are possible without  software changes.

Parameterizing via Rotary Switches 1:

Hex switch x10

Hex switch x1

Meaning

0x0 - D

0x0 - F

IP address direct via switch

0xF

0x0

IP address via DHCP server

0xF

0x1

IP address via BootP server

0xF

0x2

BootP save address

Hex switch x10

Hex switch x1

Meaning (Power ON/OFF)

0xF

0x3

Fast ModbusTCP active (only B900, B901)

0xF

0x4

Fast ModbusTCP inactive (only B900, B901)

0xF

0x5

BOOTP / DHCP Server 2.3 (Rockwell) (only B905)

0xF

0x6

reserved

0xF

0x7

reserved

0xF

0x8

reserved

0xF

0x9

reserved

0xF

0xA

reserved

0xF

0xB

reserved

0xF

0xC

deletes AMS NetID table

0xF

0xD

sets fieldbus specific default values

0xF

0xE

deletes boot project (only for Controller Box IL230x-C900)

0xF

0xF

Sets module back to manufacturer settings

Restoring the manufacturer settings

Delete the boot project (only for Controller Box IL230x-C900)

Setting the Ethernet parameters