Parameterizing via Rotary Switches
By using the rotary switches, the following parameterizations are possible without software changes.
Hex switch x10 | Hex switch x1 | Meaning |
---|---|---|
0x0 - D | 0x0 - F | IP address direct via switch |
0xF | 0x0 | IP address via DHCP server |
0xF | 0x1 | IP address via BootP server |
0xF | 0x2 | BootP save address |
Hex switch x10 | Hex switch x1 | Meaning (Power ON/OFF) |
---|---|---|
0xF | 0x3 | Fast ModbusTCP active (only B900, B901) |
0xF | 0x4 | Fast ModbusTCP inactive (only B900, B901) |
0xF | 0x5 | BOOTP / DHCP Server 2.3 (Rockwell) (only B905) |
0xF | 0x6 | reserved |
0xF | 0x7 | reserved |
0xF | 0x8 | reserved |
0xF | 0x9 | reserved |
0xF | 0xA | reserved |
0xF | 0xB | reserved |
0xF | 0xC | deletes AMS NetID table |
0xF | 0xD | sets fieldbus specific default values |
0xF | 0xE | deletes boot project (only for Controller Box IL230x-C900) |
0xF | 0xF | Sets module back to manufacturer settings |
Restoring the manufacturer settings
- Switch off the module.
- Set the rotary switches to 0xFF and switch on the module.
- After setting the default parameter successfully, the LEDs I/O RUN and I/O ERR are flashing simultaneously.
- Now you can switch off the module again, to set the IP address.
Delete the boot project (only for Controller Box IL230x-C900)
- Switch off the module.
- Set the rotary switches to 0xFE and switch on the module.
- After deleting the boot project successfully, the LEDs I/O RUN and I/O ERR are flashing simultanously.
- Now you can switch off the module again, to set the IP address.
Setting the Ethernet parameters
- Switch off the module.
- Set the rotary switches to 0xFD and switch on the module.
- The LEDs I/O RUN and I/O ERR are flashing.
- The default values of table 100 are set.
- Now you can switch off the module again, to set the IP address.