Parameterizing via Rotary Switches
By using the rotary switches, the following parameterizations are possible without software changes.
 
Hex switch x10  | Hex switch x1  | Meaning  | 
|---|---|---|
0x0 - D  | 0x0 - F  | IP address direct via switch  | 
0xF  | 0x0  | IP address via DHCP server  | 
0xF  | 0x1  | IP address via BootP server  | 
0xF  | 0x2  | BootP save address  | 
Hex switch x10  | Hex switch x1  | Meaning (Power ON/OFF)  | 
|---|---|---|
0xF  | 0x3  | Fast ModbusTCP active (only B900, B901)  | 
0xF  | 0x4  | Fast ModbusTCP inactive (only B900, B901)  | 
0xF  | 0x5  | BOOTP / DHCP Server 2.3 (Rockwell) (only B905)  | 
0xF  | 0x6  | reserved  | 
0xF  | 0x7  | reserved  | 
0xF  | 0x8  | reserved  | 
0xF  | 0x9  | reserved  | 
0xF  | 0xA  | reserved  | 
0xF  | 0xB  | reserved  | 
0xF  | 0xC  | deletes AMS NetID table  | 
0xF  | 0xD  | sets fieldbus specific default values  | 
0xF  | 0xE  | deletes boot project (only for Controller Box IL230x-C900)  | 
0xF  | 0xF  | Sets module back to manufacturer settings  | 
Restoring the manufacturer settings
- Switch off the module.
 - Set the rotary switches to 0xFF and switch on the module.
 - After setting the default parameter successfully, the LEDs I/O RUN and I/O ERR are flashing simultaneously.
 - Now you can switch off the module again, to set the IP address.
 
Delete the boot project (only for Controller Box IL230x-C900)
- Switch off the module.
 - Set the rotary switches to 0xFE and switch on the module.
 - After deleting the boot project successfully, the LEDs I/O RUN and I/O ERR are flashing simultanously.
 - Now you can switch off the module again, to set the IP address.
 
Setting the Ethernet parameters
- Switch off the module.
 - Set the rotary switches to 0xFD and switch on the module.
 - The LEDs I/O RUN and I/O ERR are flashing.
 - The default values of table 100 are set.
 - Now you can switch off the module again, to set the IP address.