Technical Data

Technical Data 1:

Technical data

IL230x-B905

Extension modules (IL....)

max. 120

Maximum number of bytes (IL....)

512Byte In- and 512 Byte Output

Transmission medium

4 x 2 twisted pair copper cable; category 3 (10 MBaud), category 5 (100 MBaud)

Transfer rate

10/100 MBaud

Topology

star shaped cabling

Distance between modules

100 meters (Hub/Switch to Fieldbus Box)

Configuration

via KS2000 or via controller

Protocols

Ethernet/IP

Power supply

Control voltage: 24VDC (-15%/+20%); load voltage: according to I/O type

Control voltage current consumption

according to I/O type + current consumption of sensors, max. 0.5 A

Load voltage current consumption

according to I/O type

Power supply connection

Feed: 1 x M8 connector 4-pin
downstream connection: 1 x M8 socket 4-polig

Connection Fieldbus

1 x M12 d-coded socket (female)

Electrical isolation

Channels / control voltage: no
between the channels: no
control voltage / fieldbus: yes

Permissible ambient temperature range during operation

0°C ... +55°C

Permissible ambient temperature range during storage

-25°C ... +85°C

Vibration / shock resistance

according to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29

EMC resistance burst / ESD

according to EN 61000-6-2 (EN 50082) / EN 61000-6-4 (EN 50081)

Protection class

IP 65/66/67 (according to EN 60529)

Installation position

variable

Approvals

CE

 

NOTICE

Note