The process image is sub-divided into input image and output image. The Coupler Box first maps all complex (byte-oriented) Extension Boxes (IE3xxx, IE4xxx, IE5xxx, IE6xxx), into the process image in the order in which they are inserted in IP-Link. Afterwards all digital Extension Boxes (IE1xxx, IE2xxx) are added to the process image.

The complex (byte-oriented) Extension Boxes are always mapped with the following settings:

  • complete evaluation
  • Word alignment
  • Intel format

Example 1:

IL2301-B900 (4DI, 4DO)
2 x IE1001 (8DI)
2 x IE2002 (8DO)
1 x IE3312 (4 AI)
1 x IE4132 (4AO)

Position

Module

Input %I..Byte Offset

Output %Q..Byte Offset

1

IE3312

0...7

0..7

2

IE4132

8...15

8...15

3

IL2301

16.0...16.3

16.0...16.3

5

IE1001

16.4...17.3

-

6

IE2002

-

16.4...17.3

 

Note

Detailed description about the mappings of the Fieldbus Box Modules can be found in the document Signal Types, Installation, Configuration of the I/O modules, that may be found on the BECKHOFF CD Products & Solutions or in the internet (http://www.beckhoff.com) under Download/Fieldbus Box.