Stromverbrauch

Für die Stromweiterleitung und der Absicherung der Module sowie bei der Betrachtung des Spannungsabfall auf der Powerleitungsversorgung ist es wichtig, den Stromverbrauch der einzelnen Module zu kennen. Die nachfolgende Tabelle enthält den Stromverbrauch bei 24 VDC.

Die Sensorversorgung bzw. der Strom für evtl. Ausgänge muss dazu addiert werden.

E/A-Type Kompakt-Box

Module

−B310

−B510, −B520

−B730, −B800, −B810

IP1000−Bxxx, IP1001−Bxxx, IP1002−Bxxx, IP1010−Bxxx, IP1011−Bxxx, IP1012−Bxxx

Is = 85 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

IP1502-Bxxx

Is = 85 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

IP2000−Bxxx, IP2001−Bxxx, IP2002−Bxxx

Is = 90 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

IP2020−Bxxx, IP2021−Bxxx, IP2022−Bxxx

Is = 90 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

IP2040−Bxxx, IP2041−Bxxx, IP2042−Bxxx

Is = 90 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

IP2300−Bxxx, IP2301−Bxxx, IP2302−Bxxx, IP2310−Bxxx, IP2311−Bxxx, IP2312−Bxxx

Is = 90 mA
Ip = 5 mA

Is = 50 mA
Ip = 5 mA

Is = 50 mA
Ip = 5 mA

IP2320−Bxxx, IP2321−Bxxx, IP2322−Bxxx, IP2330−Bxxx, IP2331−Bxxx, IP2332−Bxxx

Is = 90 mA
Ip = 5 mA

Is = 50 mA
Ip = 5 mA

Is = 50 mA
Ip = 5 mA

IP2400−Bxxx, IP2401−Bxxx

Is = 90 mA
Ip = 5 mA

Is = 50 mA
Ip = 5 mA

Is = 50 mA
Ip = 5 mA

IP2512−Bxxx

Is = 85 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

Is = 45 mA
Ip = 5 mA

IP3102−Bxxx

Is = 140 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

IP3112−Bxxx

Is = 140 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

IP3202−Bxxx

Is = 110 mA
Ip = 5 mA

Is = 70 mA
Ip = 5 mA

Is = 70 mA
Ip = 5 mA

IP3312−Bxxx

Is = 110 mA
Ip = 5 mA

Is = 70 mA
Ip = 5 mA

Is = 70 mA
Ip = 5 mA

IP4112−Bxxx

Is = 115 mA
Ip = 35 mA

Is = 85 mA
Ip = 35 mA

Is = 85 mA
Ip = 35 mA

IP4132−Bxxx

Is = 140 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

IP5009−Bxxx

Is = 140 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

IP5109−Bxxx

Is = 140 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

Is = 105 mA
Ip = 5 mA

IP5209−Bxxx

Is = 110 mA
Ip = 5 mA

Is = 70 mA
Ip = 5 mA

Is = 70 mA
Ip = 5 mA

IP6002−Bxxx

Is = 115 mA
Ip = 35 mA

Is = 85 mA
Ip = 35 mA

Is = 85 mA
Ip = 35 mA

IP6012−Bxxx

Is = 115 mA
Ip = 35 mA

Is = 85 mA
Ip = 35 mA

Is = 85 mA
Ip = 35 mA

IP6022−Bxxx

Is = 115 mA
Ip = 35 mA

Is = 85 mA
Ip = 35 mA

Is = 85 mA
Ip = 35 mA

E/A−Type Koppler Box

Module

−B310

−B510, −B520

−B730, −B800, −B810

IL2300−Bxxx, IL2301−Bxxx, IL2302−Bxxx

Is = 100 mA
Ip = 5 mA

Is = 60 mA
Ip = 5 mA

Is = 60 mA
Ip = 5 mA

IL2300−Cxxx, IL2301−Cxxx, IL2302−Cxxx

Is = 100 mA
Ip = 5 mA

−

−

E/A−Type Erweiterungsbox

Module

 

IE1000, IE1001, IE1002, IE1010, IE1011, IE1012

Is = 25 mA
Ip = 5 mA

IE1502

Is = 25 mA
Ip = 5 mA

IE2000, IE2001, IE2002

Is = 25 mA
Ip = 5 mA

IE2020, IE2021, IE2022

Is = 25 mA
Ip = 5 mA

IE23xx, IE240x

Is = 25 mA
Ip = 5 mA

IE2512

Is = 25 mA
Ip = 5 mA

IE2808

Is = 40 mA
Ip = 5 mA

IE3102

Is = 55 mA
Ip = 5 mA

IE3112

Is = 55 mA
Ip = 5 mA

IE3202

Is = 40 mA
Ip = 5 mA

IE3312

Is = 40 mA
Ip = 5 mA

IE4112

Is = 40 mA
Ip = 5 mA

IE4132

Is = 40 mA
Ip = 5 mA

IE5009

Is = 55 mA
Ip = 5 mA

IE5109

Is = 55 mA
Ip = 5 mA

IE6002

Is = 40 mA
Ip = 5 mA

IE6012

Is = 40 mA
Ip = 5 mA

IE6022

Is = 40 mA
Ip = 5 mA