Preset Single Register (Function 6)

The Preset Single Register function can be used to access the output process image and the interface.

The first analog output is written with function 6. The analog outputs start at an offset of 0x0800. Here again the offset always describes a word. This means offset 0x0803 refers to the fourth word in the output process image.

Query

Byte Name

Modbus RTU

Modbus ASCII

Start - Frame

- 

- 

":"

0x3A

Address

11

0x0B

"0B"

0x30, 0x42

Function-Code

6

0x06

"06"

0x30, 0x36

Start-Address high

8

0x06

"06"

0x30, 0x36

Start-Address low

0

0x00

"00"

0x30, 0x30

Data high

63

0x3F

"3F"

0x33, 0x46

Data low

255

0xFF

"FF"

0x46, 0x46

Error Check, LRC/CRC

 

0xDA, 0xB0 

"A9"

0x41, 0x39

End - Frame

 

t1-t2-t3

CRLF

0x0D, 0x0A

The Fieldbus Coupler replies with the same telegram and confirmation of the received value.

Response

Byte Name

Modbus RTU

Modbus ASCII

Start - Frame

- 

- 

":"

0x3A

Address

11

0x0B

"0B"

0x30, 0x42

Function-Code

6

0x06

"06"

0x30, 0x36

Start-Address high

8

0x06

"06"

0x30, 0x36

Start-Address low

0

0x00

"00"

0x30, 0x30

Data high

63

0x3F

"3F"

0x33, 0x46

Data low

255

0xFF

"FF"

0x46, 0x46

Error Check, LRC/CRC

 

0xDA, 0xB0 

"A9"

0x41, 0x39

End - Frame

 

t1-t2-t3

CRLF

0x0D, 0x0A