Modules - Technical Data
|
Technical data |
IPxxxx-B730 |
IL230x-B730 |
|---|---|---|
|
Extension modules |
- |
Max. 120 with altogether 512 bytes input and 512 bytes output |
|
Digital peripheral signals |
according to I/O type |
max. 960 inputs and outputs |
|
Analog peripheral signals |
according to I/O type |
max. 255 inputs and outputs |
|
Configuration facilities |
via KS2000 or address switch | |
|
Bus nodes |
69 | |
|
Topology |
Line | |
|
Transmission Physics |
RS 485 (like Profibus) shielded, twisted pairs | |
|
Max. cable length |
1200 m | |
|
Protocol |
RTU (ASCII) | |
|
Baud rate |
150 to 38400 Baud (default: 9,6 kBaud) | |
|
Power supply connection |
Control voltage: 24V DC (-15%/+20%); load voltage: according to I/O type | |
|
Control voltage current consumption |
according to I/O type + current consumption of sensors, max. 0.5 A | |
|
Load voltage current consumption |
according to I/O type | |
|
Load voltage current consumption |
Feed: 1 x M8 connector, 4-pin | |
|
Fieldbus connection |
1 x M12 socket, 5-pin, (inverse coding) | |
|
Electrical isolation |
Channels/control voltage: no | |
|
Operating temperature |
0°C ... +55°C | |
|
Storage temperature |
-25°C ... +85°C | |
|
Vibration / shock resistance |
conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29 | |
|
EMC resistance burst / ESD |
conforms to EN 61000-6-2 / EN 61000-6-4 | |
|
Protection class |
IP 65/66/67 (according EN 60529) | |
|
Installation position |
any | |
|
Approval |
CE, UL E172151 | |