Reaction to IP-Link Errors
The error reaction can be set for an IP-Link error (such as pulling out the plug). The possible reactions are:
- Data exchange is stopped.
- Profibus inputs become 0
- Profibus inputs are retained unchanged
The settings for the reaction to Profibus error function are found in byte 10 of the User_Prm_Data (default settings are printed bold):
Byte |
Bit |
Description |
is supported by |
---|---|---|---|
10 |
2, 3 |
Reaction to Profibus errors |
IL230x-B3xx |
In TwinCAT the settings for the Reaction to IP-Link error can be transferred with ADSRead and ADSWrite (ADS: Automation Device Specification). For this purpose they should be activated in the User_Prm_Data.
The settings for the Reaction to IP-Link error function are found in the TwinCAT System Manager on the "PrmData" tab for the corresponding Bus Coupler.