Feature Register (R32) IP/IE4132
The module's fundamental settings can be modified in the feature register. Write protection must first be cancelled in the code-word register before it is possible to write into this register.
|
Bit |
Value |
Description |
Manufacturer’s setting |
|---|---|---|---|
|
0 |
0bin |
User scaling is inactive |
0bin |
|
1bin |
User scaling is active | ||
|
1 |
0bin |
Manufacturer scaling is inactive |
0bin |
|
1bin |
Manufacturer scaling is inactive | ||
|
2 |
0bin |
Watchdog timer active. |
0bin |
|
1bin |
Watchdog timer inactive. | ||
|
3 |
0bin |
reserved |
0bin |
|
... |
... |
... |
... |
|
7 |
0bin |
reserved |
0bin |
|
8 |
0bin |
Manufacturer switch-on value [0] |
0 |
|
1bin |
User switch-on value R35 | ||
|
9 |
0bin |
reserved |
0bin |
|
... |
... |
... |
... |
|
15 |
0bin |
reserved |
0bin |
Explanation of the watchdog timer
The watchdog timer is switched on by default. If the watchdog overflows, then either the manufacturer's or the user's switch-on value is output by the module.