Feature Register (R32) IP/IE3102
The module's fundamental settings can be modified in the
feature register. Write protection must first be cancelled in the
code-word register before it is possible to write into this
register.
Default [0x0010]
|
Bit |
Value |
Description |
Manufacturer’s setting |
|---|---|---|---|
|
0 |
0bin |
User scaling is inactive |
0bin |
|
1bin |
User scaling is active | ||
|
1 |
0bin |
Manufacturer scaling is inactive |
0bin |
|
1bin |
Manufacturer scaling is active | ||
|
2 |
0bin |
reserved |
0bin |
|
3 |
0bin |
The arithmetic sign of numerical quantities is not represented |
0bin |
|
1bin |
The arithmetic sign of numerical quantities is active (-1 = 0x8001) | ||
|
4 |
0bin |
Overflow offset is inactive: |
1bin |
|
1bin |
Overflow offset is active: | ||
|
5 |
0bin |
reserved |
0bin |
|
... |
... |
... |
... |
|
8 |
0bin |
reserved |
0bin |
|
9 |
0bin |
Limit value 1 is inactive |
0bin |
|
1bin |
Limit value 1 is active (the limit value 1 is specified in Register R35) | ||
|
10 |
0bin |
Limit value 2 is inactive |
0bin |
|
1bin |
Limit value 2 is active (the limit value 2 is specified in Register R36) | ||
|
11 |
0bin |
reserved |
0bin |
|
... |
... |
... |
... |
|
15 |
0bin |
reserved |
0bin |