Assembling of the ZS1022-0010 IP-Link Plug (clip type)
Preparation (Exploded view)
|
|
A: fiber optic |
|
B: outer jacket | |
|
C: Kevlar fiber | |
|
D: fiber jacket | |
|
E: fiber core | |
|
F: locking cap | |
|
G: O-ring | |
|
H: sleeve | |
|
I: connector housing |
- Strip cable jacket according to indicated lengths of outer and
fiber jacket.
ATTENTION:
The fiber core should not be damaged! - Cut the Kevlar fiber to the same length of the outer
jacket.
ATTENTION:
In order to reach maximum clamping force outer and fiber jacket have to be free of deformation (scores, etc.) as well as of grease, oil and lubricant.
Assembly
|
|
- Pull the sleeve over the outer jacket and the O-ring over the locking cap.
- Insert the prepared fiber-optic in the connector housing until outer jacket hits L and fiber jacket hits K simultaneously.
- Align the connector housing as required in order to prevent a possible torsion of cable.
- Pull the sleeve over the connector housing until it radially latches.
- Press the locking cap into the connector housing until all 4 nibs latch. This operation can be implemented without tools or with corresponding pliers. Keep correct mounting position M of the locking cap. The correct mounting of the O-ring can be checked with the latching holes N.
Surface treatment
|
|
- Treat the fiber core with grinding gauge O up to the
final dimension and intended quality.
For this purpose take sand paper with grain size 600, and work on a smooth surface. - Insert the mounted connector in the grinding gauge and treat the surface with a rotary movement.
- Remove grinding dust with a clean lint-free cloth.
- Check the quality of the grinded surface.
The surface has to be smooth and free of scratches, grooves and splinters.
Disassembly
|
|
- Apply appropriate tool at cut-out P or Q.
- Lift out the locking cap from the closed connector
housing.
ATTENTION:
Damaged or deformed components should not be applied again after disassembly. - Prepare fiber-optic sensor after disassembly according to point 1 again.
Ordering note
ZS1022-0010: IP-Link connector (clip type), packaging unit 10 items