Preparing the IP-Link cable
Required tools:
- Side cutter
- Stripping tool
- Abrasive paper (grain size 600)
NOTICE | ||
During stripping of the insulation and installation please ensure that
| ||
Fixing the fiber core for preparing
IP Link Connector
IP-Link connector (1) with cap (2)
Preparing the cable end
- First slide the cap of the IP-Link connector (2) onto the optical fiber cable.
- Shorten the orange-colored outer sheath (A) by approximately 23 mm without damaging the Kevlar fibers (K) below.
- Shorten the Kevlar (K) to approx. 19 mm.
- Fold back the yellow Kevlar fibers (K) over the outer sheath (A).
- Shorten the black fiber sheath (U) by approximately 17 mm without damaging the optical fiber (L) below.
Installation of the IP-Link connector
- Slide the IP-Link connector (1) onto the optical fiber cable until it is in contact with the Kevlar fibers (4) that were folded over the outer sheath (3).
- Screw the connector clockwise onto the outer sheath until it cannot be turned further by hand (hand-tight). Do not use any tools! The plug is designed to cut a thread into the black fiber sheath (5) during this process.
If the cable was stripped correctly, the optical fiber (6) now protrudes approximately 8 mm from the IP-Link connector (1). - Cut the Kevlar fibers protruding from the back of the IP-Link connector without damaging the outer sheath.
- Slide the cap (2) on the optical fiber cable against the IP-Link connector (1) from behind until it engages.
- Cut the optical fiber protruding from the front of the IP-Link connector approximately 2 mm from the tip of the connector. Be careful not to cut shorter, since the fiber is very hard and can splitter.
- Sand the optical fiber with abrasive paper, grain size 600, until only approximately 0.4 mm protrude from the tip of the connector. Avoid damaging the connector!
- Remove any grinding dust and an eventual burr using a clean, lint-free cloth.
Checking the fiber ends (visual inspection)
Check the sanded fiber ends:
- The end of the optical fiber cable must have a clean, level surface at right angles to the connector guide, protruding approximately 0.4 mm from the tip of the connector.
- Point one cable end to a light source. At the other cable end, no scratches, cracks or splintering should be visible in the illuminated fiber.
Order information
ZS1020-0010: IP-Link connector, packaging unit 1 item
ZS1021-0010: IP-Link connector, packaging unit 10 items