The mapping concept

EtherCAT slaves are directly linked in the System Manager with the process image of a task. This leads to so-called synchronous mapping, i.e. write/read access to the process image takes place alternately through I/O update/fieldbus and task.

The mapping concept 1:Fig.250: System Manager icons for synchronous/asynchronous mapping

With asynchronous mapping the two processes “Task” and “Fieldbus Update” access the process image in their respective cycle time.

Link effect

If I/Os are linked directly with a task, the corresponding EtherCAT fieldbus update takes place synchronous with this task cycle time. No more than “max. Sync Task” I/O cycles are executed. (EtherCAT master -->  advanced settings --> cyclic task).

If devices are not linked with a task, they are controlled via asynchronous mapping based on the slowest available task. This is also the case with automatically set up cross communication, for example in safety devices.

The mapping concept 2:

Watchdog

Check the mapping settings to ensure that timings set up in this way do not exceed the watchdog times.
Watchdog examples:

    • I/O watchdog: default 100 ms
    • FSoE watchdog: 100 ms (confirmed communication, cycle times <= 25 ms recommended with default setting)

     

    The mapping concept 3:Fig.251: Automatically set-up asynchronous mapping