Setting the IP address
The ER9320-0022 has no predefined IP address. The IP address can be assigned by any of the following network devices:
- PROFINET controller (normal case)
- DHCP server
Before commissioning, use the S1 rotary switch to set the network device that should assign the IP address.
S1 | Source of the IP address |
|---|---|
1 | DHCP server |
3 | PROFINET controller |
The setting of the rotary switch is only applied during start-up. If you adjust the rotary switch during operation, the new value will only take effect upon the next start.