Troubleshooting

Check the structure of the Hot Connect group

The box with ID switch must be the first device in the Hot Connect group.
The first EtherCAT device in a Hot Connect group is marked with a red “HC” symbol.

Troubleshooting 1:

If an EtherCAT device other than the box with ID switch is marked with a red “HC” symbol, proceed as follows:

1. In the Solution Explorer, right-click on the EtherCAT device with the red “HC” symbol.
2. Click on "Delete from Hotconnect group" in the context menu.
3. Create the Hot Connect group correctly. See chapter Creating a Hot Connect group.

Check the addressing method

1. Click on the box with the ID switch in the Solution Explorer.
2. Select the “Hot Connect” tab.
3. Click the "Configure" button.
4. Ensure that "Explicit Device Identification" is selected.
Troubleshooting 2: