Set the threshold values
Note | |
Critical operating states may not be reported under certain circumstances. If you set the threshold values for warning messages and error messages incorrectly, EPP9022 may not inform you of critical operating states:
|
You can set the threshold values for warning messages and error messages via the CoE parameters shown in the following tables. Observe the recommended value range.
Input channel 1: Control voltage US
Reason for | Type of message | CoE parameters for setting the threshold value | Unit | Recommended | Factory |
|---|---|---|---|---|---|
Undervoltage | Warning message | 8000:14 | mV | min. 20400dec | 20400dec |
Error message | 8000:11 | mV | min. 18000dec | 18000dec | |
Overvoltage | Warning message | 8000:15 | mV | max. 28800dec | 28800dec |
Error message | 8000:12 | mV | max. 30000dec | 30000dec | |
Overcurrent | Warning | 8000:16 | mA | 0 .. 2500dec | 2500dec |
Error message | 8000:13 | mA | 0 .. 3000dec | 3000dec |
Input channel 2: Peripheral voltage UP
Reason for | Type of message | CoE parameters for setting the threshold value | Unit | Recommended | Factory |
|---|---|---|---|---|---|
Undervoltage | Warning message | 8010:14 | mV | min. 20400dec | 20400dec |
Error message | 8010:11 | mV | min. 18000dec | 18000dec | |
Overvoltage | Warning message | 8010:15 | mV | max. 28800dec | 28800dec |
Error message | 8010:12 | mV | max. 30000dec | 30000dec | |
Overcurrent | Warning | 8010:16 | mA | 0 .. 2500dec | 2500dec |
Error message | 8010:13 | mA | 0 .. 3000dec | 3000dec |