Standard objects

Index 1000 Device type

Access rights: read only

Subindex (hex)

Name

Description

Data type

Value

-

Device type

Bit 0 .. 15: Device profile number
Bit 16 .. 31: Module profile number

(Device profile number 5001: Modular Device Profile MDP)

UDINT

5001dec

Index 1008 Device name

Access rights: read only

Subindex (hex)

Name

Description

Data type

Value

-

Device name

Name of the EtherCAT device

STRING

EPP9022-9060

Index 1009 Hardware version

Access rights: read only

Subindex (hex)

Name

Description

Unit

Data type

Value

-

Hardware version

Hardware version of the EtherCAT device

-

STRING

1)

Index 100A Software version

Access rights: read only

Subindex (hex)

Name

Description

Unit

Data type

Value

-

Software version

Firmware version of the EtherCAT device

-

STRING

1)

Index 1011 Restore default parameters

Access rights: read/write

Subindex (hex)

Name

Description

Data type

Default

1

Subindex 001

Resets the CoE parameters to the factory settings.

To do this, write the value 0x64616F6C in this parameter.

UDINT

0

Index 1018 Identity

Access rights: read only

Subindex (hex)

Name

Description

Data type

Value

01

Vendor ID

Vendor identifier (2 = Beckhoff Automation)

UDINT

2

02

Product code

Product code

UDINT

1685584361dec

03

Revision

Bit 0 … 15: Index number of the product variant
Bit 16 … 31: Revision of the device description (ESI)

UDINT

Bit 0 … 15: 9060dec

04

Serial number

(not used)

UDINT

0

Index 10F0 Backup parameter handling

Access rights: read only

Subindex (hex)

Name

Description

Data type

Value

01

Checksum

Checksum of the backup parameters.

Backup parameters are the CoE objects whose content is reset to the factory setting by the CoE index 1011.

UDINT

11102dec