Voltage measurement output

You can check the supply voltages manually at the voltage measurement output, for example using a multimeter.

Voltage measurement output 1:

An unsuitable measuring device can falsify the measurement.

The measurement will be falsified if the input resistance of the connected measuring device is too small.

  • Use a measuring device that meets the requirements in the technical data.
Voltage measurement output 2:

The measurement output cannot be used as a supply voltage output

The output voltages will collapse if they are loaded.

  • Do not use the measurement output as a supply voltage output.
    If you wish to decouple the supply voltages from an EtherCAT P signal, use an EPP9001-0060, for example.
Voltage measurement output 3:
Voltage measurement output, M8 socket

Contact

Potential

Description

Core color 1)

1

US1

Control voltage

Brown

2

UP1

Peripheral voltage

White

3

GNDS

Reference ground to US1

Blue

4

GNDP

Reference ground to UP1

Black

1) The core colors apply to cables of the type: Beckhoff ZK2020-xxxx-xxxx