Configuration data (vendor-specific)
Index F80F DCM Vendor data
Index (hex)  | Name  | Meaning  | Data type  | Flags  | Default  | 
|---|---|---|---|---|---|
F80F:0  | DCM Vendor data  | Max. Subindex  | UINT8  | RO  | 0x06 (6dec)  | 
F80F:01  | PWM Frequency  | DC link frequency  | UINT16  | RW  | 0x7530 (30000dec)  | 
F80F:02  | Deadtime  | Dead time for pulse width modulation  | UINT16  | RW  | 0x0102 (258dec)  | 
F80F:03  | Deadtime space  | Duty cycle limitation  | UINT16  | RW  | 0x0009 (9dec)  | 
F80F:04  | Warning temperature  | Threshold of the temperature warning  | INT8  | RW  | 0x50 (80dec)  | 
F80F:05  | Switch off temperature  | Switch-off temperature  | INT8  | RW  | 0x64 (100dec)  | 
F80F:06  | Analog trigger point  | Trigger point for AD conversion  | UINT16  | RW  | 0x000A (10dec)  |