Position lag monitoring
The position lag monitoring function checks whether the current position lag of an axis has exceeded the limit value. The position lag is the difference between the setpoint (control value) and the actual value reported back. Suboptimal parameter settings can lead to an error in position lag monitoring during the axis movement. During commissioning it may therefore be advisable to increase the "Maximum Position Lag Value" slightly.
Notice | |
CAUTION: Damage to equipment, machines and peripheral components possible! Setting the position lag monitoring parameters too high may result in damage to equipment, machines and peripheral components. |
