Adaptation of current and voltage
Notice | |
Risk of material damage due to incorrect configuration Incorrect configuration can cause damage due to overcurrent.
|
Notice | |
The motor may overheat In order to prevent overheating of the connected motor it is important to adapt the current and voltage output of the box to the motor. |
Index 0x8020:02 "Nominal current" and index 0x8020:03 "Nominal voltage" have be set appropriately in the CoE register. In addition, you should also adapt the "Maximal current" in the index 0x8020:01 and the coil resistance of the motor in the index 0x8020:04 "Motor coil resistance" to the connected motor.
Reducedcurrent can be set in index 0x8020:05 and 0x8020:06. This reduces the coil current when at a standstill (and therefore the power dissipation). Please note that this reduces the torque.