Parameterizing the NC axis
Parameter "Reference Velocity"
Unit: °/s
Factory setting: 2200dec
Calculate the "Reference Velocity" using this formula:
|
| nref: "Reference Velocity" [°/s] fmax: "Speed range" [full steps/s] φ: Step angle of the motor [°] |
Example for an AS1050-0120 motor:
|
|
Setting the acceleration time
In order to pass through any resonances that may occur as quickly as possible, the ramps for the acceleration time and the deceleration time should be as steep as possible.
Note | |
Short braking times can lead to overvoltages in the DC link. In the event of an overvoltage in the DC link, a protective mechanism switches off the motor output stage. The "Error" status bit in the process data object STM status is set.
|
Further Information

