Connectors
Notice | |
Risk of damage to the device! Bring the EtherCAT/EtherCAT P system into a safe, powered down state before starting installation, disassembly or wiring of the modules! |
Two M8 sockets at the upper end of the modules are provided for supply and downstream connection of EtherCAT P:
- IN: left M8 socket for EtherCAT P supply
- OUT: right M8 socket for downstream connection of EtherCAT P
The metal threads of the M8 EtherCAT P sockets are internally linked to the FE connection via high impedance RC combination. See chapter Functional earth.
Contact | Signal | Voltage | Core color 1) |
|---|---|---|---|
1 | Tx + | GNDS | yellow |
2 | Rx + | GNDP | white |
3 | Rx - | UP: peripheral voltage, +24 VDC | blue |
4 | Tx - | US: control voltage, +24 VDC | orange |
Housing | Shield | Shield | Shield |
1) The core colors apply to EtherCAT P cables and ECP cables from Beckhoff.