Restoring the delivery state
To restore the delivery state for backup objects in ELxxxx terminals / EPxxxx- and EPPxxxx box modules, the CoE object Restore default parameters, SubIndex 001 can be selected in the TwinCAT System Manager (Config mode).

Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value 1684107116 in field Dec or the value 0x64616F6C in field Hex and confirm with OK.
All backup objects are reset to the delivery state.

![]() | Alternative restore value In some older terminals / boxes the backup objects can be switched with an alternative restore value: An incorrect entry for the restore value has no effect. |
