Profile-specific objects

Index 6000 COM Inputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6000:0

COM Inputs Ch.1

 

UINT8

RO

0x26 (38dec)

6000:01

Transmit accepted

The module acknowledges receipt of data by changing the state of this bit

BOOLEAN

RO

0x00 (0dec)

6000:02

Receive request

By changing the state of this bit, the module informs the controller that the DataIn bytes contain the number of bytes displayed in "Input length"

BOOLEAN

RO

0x00 (0dec)

6000:03

Init Accepted

The initialization is carried out from the terminal

BOOLEAN

RO

0x00 (0dec)

6000:04

Buffer full

The receive FIFO is full

BOOLEAN

RO

0x00 (0dec)

6000:05

Parity error

A parity error has occurred

BOOLEAN

RO

0x00 (0dec)

6000:06

Framing error

A framing error has occurred

BOOLEAN

RO

0x00 (0dec)

6000:07

Overrun error

An overrun error has occurred

BOOLEAN

RO

0x00 (0dec)

6000:09

Input length

Number of input bytes available for transfer from the terminal to the controller

UINT8

RO

0x00 (0dec)

6000:11

Data In 0

Input data

UINT8

RO

0x00 (0dec)

6000:12

Data In 1

Input data

UINT8

RO

0x00 (0dec)

6000:13

Data In 2

Input data

UINT8

RO

0x00 (0dec)

6000:14

Data In 3

Input data

UINT8

RO

0x00 (0dec)

6000:15

Data In 4

Input data

UINT8

RO

0x00 (0dec)

6000:16

Data In 5

Input data

UINT8

RO

0x00 (0dec)

6000:17

Data In 6

Input data

UINT8

RO

0x00 (0dec)

6000:18

Data In 7

Input data

UINT8

RO

0x00 (0dec)

6000:19

Data In 8

Input data

UINT8

RO

0x00 (0dec)

6000:1A

Data In 9

Input data

UINT8

RO

0x00 (0dec)

6000:1B

Data In 10

Input data

UINT8

RO

0x00 (0dec)

6000:1C

Data In 11

Input data

UINT8

RO

0x00 (0dec)

6000:1D

Data In 12

Input data

UINT8

RO

0x00 (0dec)

6000:1E

Data In 13

Input data

UINT8

RO

0x00 (0dec)

6000:1F

Data In 14

Input data

UINT8

RO

0x00 (0dec)

6000:20

Data In 15

Input data

UINT8

RO

0x00 (0dec)

6000:21

Data In 16

Input data

UINT8

RO

0x00 (0dec)

6000:22

Data In 17

Input data

UINT8

RO

0x00 (0dec)

6000:23

Data In 18

Input data

UINT8

RO

0x00 (0dec)

6000:24

Data In 19

Input data

UINT8

RO

0x00 (0dec)

6000:25

Data In 20

Input data

UINT8

RO

0x00 (0dec)

6000:26

Data In 21

Input data

UINT8

RO

0x00 (0dec)

Index 6001 Status Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6001:0

Status Ch.1

 

UINT8

RO

0x01 (1dec)

6001:01

Status

Status word for compatible process image

UINT16

RO

0x0000 (0dec)

Index 6010 DIG Inputs

Index (hex)

Name

Meaning

Data type

Flags

Default

6010:0

DIG Inputs

 

UINT8

RO

0x02 (2dec)

6010:01

Digital Input 1

 

BOOLEAN

RO

0x00 (0dec)

6010:02

Digital Input 1

 

BOOLEAN

RO

0x00 (0dec)

6010:03

Init Accepted

The initialization is carried out from the terminal

BOOLEAN

RO

0x00 (0dec)

Index 7000 COM Outputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

7000:0

COM Outputs Ch.1

 

UINT8

RO

0x26 (38dec)

7000:01

Transmit request

By changing the state of this bit, the controller informs the terminal that the DataOut bytes contain the number of bytes displayed in "Output length".

BOOLEAN

RO

0x00 (0dec)

7000:02

Receive accepted

The controller acknowledges receipt of data by changing the state of this bit.

BOOLEAN

RO

0x00 (0dec)

7000:03

Init request

The controller requests the module to initialize.

BOOLEAN

RO

0x00 (0dec)

7000:04

Send continuous

Continuous sending of data from the FIFO.

BOOLEAN

RO

0x00 (0dec)

7000:09

Output length

Number of output bytes available for transfer from the controller to the terminal.

UINT8

RO

0x00 (0dec)

7000:11

Data Out 0

Output data

UINT8

RO

0x00 (0dec)

7000:12

Data Out 1

Output data

UINT8

RO

0x00 (0dec)

7000:13

Data Out 2

Output data

UINT8

RO

0x00 (0dec)

7000:14

Data Out 3

Output data

UINT8

RO

0x00 (0dec)

7000:15

Data Out 4

Output data

UINT8

RO

0x00 (0dec)

7000:16

Data Out 5

Output data

UINT8

RO

0x00 (0dec)

7000:17

Data Out 6

Output data

UINT8

RO

0x00 (0dec)

7000:18

Data Out 7

Output data

UINT8

RO

0x00 (0dec)

7000:19

Data Out 8

Output data

UINT8

RO

0x00 (0dec)

7000:1A

Data Out 9

Output data

UINT8

RO

0x00 (0dec)

7000:1B

Data Out 10

Output data

UINT8

RO

0x00 (0dec)

7000:1C

Data Out 11

Output data

UINT8

RO

0x00 (0dec)

7000:1D

Data Out 12

Output data

UINT8

RO

0x00 (0dec)

7000:1E

Data Out 13

Output data

UINT8

RO

0x00 (0dec)

7000:1F

Data Out 14

Output data

UINT8

RO

0x00 (0dec)

7000:20

Data Out 15

Output data

UINT8

RO

0x00 (0dec)

7000:21

Data Out 16

Output data

UINT8

RO

0x00 (0dec)

7000:22

Data Out 17

Output data

UINT8

RO

0x00 (0dec)

7000:23

Data Out 18

Output data

UINT8

RO

0x00 (0dec)

7000:24

Data Out 19

Output data

UINT8

RO

0x00 (0dec)

7000:25

Data Out 20

Output data

UINT8

RO

0x00 (0dec)

7000:26

Data Out 21

Output data

UINT8

RO

0x00 (0dec)

Index 7001 Ctrl Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

7001:0

Ctrl Ch.1

 

UINT8

RO

0x01 (1dec)

7001:01

Ctrl

Control word for compatible process image

UINT16

RO

0x0000 (0dec)

Index 7010 DIG Outputs

Index (hex)

Name

Meaning

Data type

Flags

Default

7010:0

DIG Outputs

 

UINT8

RO

0x26 (38dec)

7010:01

Digital Output 1

 

BOOLEAN

RO

0x00 (0dec)

7010:02

Digital Output 2

 

BOOLEAN

RO

0x00 (0dec)

Index A000 COM Diag data Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

A000:0

COM Diag data Ch.1

 

UINT8

RO

0x21 (33dec)

A000:01

Buffer overflow

A buffer overflow has occurred.

BOOLEAN

RO

0x00 (0dec)

A000:02

Parity error

A parity error has occurred.

BOOLEAN

RO

0x00 (0dec)

A000:03

Framing error

A framing error has occurred.

BOOLEAN

RO

0x00 (0dec)

A000:04

Overrun error

An overrun error has occurred.

BOOLEAN

RO

0x00 (0dec)

A000:05

Buffer full

The receive FIFO is full.

BOOLEAN

RO

0x00 (0dec)

A000:11

Data bytes in send buffer

Number of data bytes in the send FIFO

UINT16

RO

0x0000 (0dec)

A000:21

Data bytes in receive buffer

Number of data bytes in the receive FIFO

UINT16

RO

0x0000 (0dec)

Index F000 Modular device profile

Index (hex)

Name

Meaning

Data type

Flags

Default

F000:0

Modular device profile

General information for the modular device profile

UINT8

RO

0x02 (2dec)

F000:01

Module index distance

Index distance of the objects of the individual channels

UINT16

RO

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RO

0x0002 (2dec)

Index F008 Code word

Index (hex)

Name

Meaning

Data type

Flags

Default

F008:0

Code word

 

UINT32

RW

0x00000000 (0dec)

Index F010 Module list

Index (hex)

Name

Meaning

Data type

Flags

Default

F010:0

Module list

 

UINT8

RW

0x02 (2dec)

F010:01

SubIndex 001

 

UINT32

RW

0x00000258 (600dec)

F010:02

SubIndex 002

 

UINT32

RW

0x00000118 (280dec)