Objects to be parameterized during commissioning
Index 1011 Restore default parameters
Index (hex) | Name | Meaning | Data type | Flags | Default |
|---|---|---|---|---|---|
1011:0 | Restore default parameters | Restore default parameters | UINT8 | RO | 0x01 (1dec) |
1011:01 | SubIndex 001 | If this object is set to "0x64616F6C" in the set value dialog, all backup objects are reset to their delivery state. | UINT32 | RW | 0x00000000 (0dec) |
Index 8010 Safe state active
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8010:0 | Safe state active |
| UINT8 | RO | 0x02 (2dec) | |
8010:01 | Output 1 | 0 | Output State will remain unchanged during OP-> SafeOP | BOOLEAN | RW | 0x00 (0dec) |
1 | Output will go to Safe State during OP-> SafeOP | |||||
8010:02 | Output 2 | 0 | Output State will remain unchanged during OP-> SafeOP | BOOLEAN | RW | 0x00 (0dec) |
1 | Output will go to Safe State during OP-> SafeOP | |||||
Index 8011 Safe state value
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8011:0 | Safe state value |
| UINT8 | RO | 0x02 (2dec) | |
8011:01 | Output 1 | 0 | Output -> 0 in case of Safe State condition | BOOLEAN | RW | 0x00 (0dec) |
1 | Output -> 1 in case of Safe State condition | |||||
8011:02 | Output 2 | 0 | Output -> 0 in case of Safe State condition | BOOLEAN | RW | 0x00 (0dec) |
1 | Output -> 1 in case of Safe State condition | |||||
Index 8020 AI settings Ch.1 (parameterization of channel 1)
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8020:0 | AI Settings Ch.1 | Maximum subindex | UINT8 | RO | 0x19 (25dec) | |
8020:01 | Enable user scale | 1 | User scale is active. | BOOLEAN | RW | 0x00 (0dec) |
8020:06 | Enable filter | 1 | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x01 (1dec) |
8020:07 | Enable limit 1 | 1 | Limit 1 enabled | BOOLEAN | RW | 0x00 (0dec) |
8020:08 | Enable limit 2 | 1 | Limit 2 enabled | BOOLEAN | RW | 0x00 (0dec) |
8020:0A | Enable user calibration | 1 | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8020:0B | Enable vendor calibration | 1 | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8020:11 | User scale offset | User scale offset | INT32 | RW | 0x00000000 (0dec) | |
8020:12 | User scale gain | User scale gain. | INT32 | RW | 0x00010000 (65536dec) | |
8020:13 | Limit 1 | First limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8020:14 | Limit 2 | Second limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8020:15 | Filter settings | This object determines the digital filter settings for all channels of the module, if it is activated via Enable filter (index 0x80n0:06). The possible settings are sequentially numbered. | UINT16 | RW | 0x0000 (0dec) | |
0 | 50 Hz FIR | |||||
1 | 60 Hz FIR | |||||
2 | IIR 1 | |||||
3 | IIR 2 | |||||
4 | IIR 3 | |||||
5 | IIR 4 | |||||
6 | IIR 5 | |||||
7 | IIR 6 | |||||
8 | IIR 7 | |||||
9 | IIR 8 | |||||
8020:17 | User calibration offset |
| INT32 | RW | 0x00000000 (0dec) | |
8020:18 | User calibration gain |
| INT16 | RW | 0x4000 (16384dec) | |
8020:19 | Range | Permissible values: | UINT16 | RW | 0x0008 (8dec) | |
8 | Differential pressure measurement relative to the reference sensor | |||||
7 | Absolute pressure measurement | |||||
Index 8030 AI settings Ch.2 (parameterization of channel 2)
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8030:0 | AI Settings Ch.2 | Maximum subindex | UINT8 | RO | 0x19 (25dec) | |
8030:01 | Enable user scale | 1 | User scale is active. | BOOLEAN | RW | 0x00 (0dec) |
8030:06 | Enable filter | 1 | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x01 (1dec) |
8030:07 | Enable limit 1 | 1 | Limit 1 enabled | BOOLEAN | RW | 0x00 (0dec) |
8030:08 | Enable limit 2 | 1 | Limit 2 enabled | BOOLEAN | RW | 0x00 (0dec) |
8030:0A | Enable user calibration | 1 | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8030:0B | Enable vendor calibration | 1 | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8030:11 | User scale offset | User scale offset | INT32 | RW | 0x00000000 (0dec) | |
8030:12 | User scale gain | User scale gain. | INT32 | RW | 0x00010000 (65536dec) | |
8030:13 | Limit 1 | First limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8030:14 | Limit 2 | Second limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8030:15 | Filter settings | This object shows the digital filter settings. The filter settings can only be read here. They are set via channel 1 for all channels of the module. | UINT16 | RW | 0x0000 (0dec) | |
0 | 50 Hz FIR | |||||
1 | 60 Hz FIR | |||||
2 | IIR 1 | |||||
3 | IIR 2 | |||||
4 | IIR 3 | |||||
5 | IIR 4 | |||||
6 | IIR 5 | |||||
7 | IIR 6 | |||||
8 | IIR 7 | |||||
9 | IIR 8 | |||||
8030:17 | User calibration offset |
| INT32 | RW | 0x00000000 (0dec) | |
8030:18 | User calibration gain |
| INT16 | RW | 0x4000 (16384dec) | |
8030:19 | Range | Permissible values: | UINT16 | RW | 0x0008 (8dec) | |
8 | Differential pressure measurement relative to the reference sensor | |||||
7 | Absolute pressure measurement | |||||
Index 8040 AI settings Ch.3 (parameterization of channel 3)
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8040:0 | AI Settings Ch.3 | Maximum subindex | UINT8 | RO | 0x19 (25dec) | |
8040:01 | Enable user scale | 1 | User scale is active. | BOOLEAN | RW | 0x00 (0dec) |
8040:06 | Enable filter | 1 | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x01 (1dec) |
8040:07 | Enable limit 1 | 1 | Limit 1 enabled | BOOLEAN | RW | 0x00 (0dec) |
8040:08 | Enable limit 2 | 1 | Limit 2 enabled | BOOLEAN | RW | 0x00 (0dec) |
8040:0A | Enable user calibration | 1 | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8040:0B | Enable vendor calibration | 1 | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8040:11 | User scale offset | User scale offset | INT32 | RW | 0x00000000 (0dec) | |
8040:12 | User scale gain | User scale gain. | INT32 | RW | 0x00010000 (65536dec) | |
8040:13 | Limit 1 | First limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8040:14 | Limit 2 | Second limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8040:15 | Filter settings | This object shows the digital filter settings. The filter settings can only be read here. They are set via channel 1 for all channels of the module. | UINT16 | RW | 0x0000 (0dec) | |
0 | 50 Hz FIR | |||||
1 | 60 Hz FIR | |||||
2 | IIR 1 | |||||
3 | IIR 2 | |||||
4 | IIR 3 | |||||
5 | IIR 4 | |||||
6 | IIR 5 | |||||
7 | IIR 6 | |||||
8 | IIR 7 | |||||
9 | IIR 8 | |||||
8040:17 | User calibration offset |
| INT32 | RW | 0x00000000 (0dec) | |
8040:18 | User calibration gain |
| INT16 | RW | 0x4000 (16384dec) | |
8040:19 | Range | Permissible values: | UINT16 | RW | 0x0008 (8dec) | |
8 | Differential pressure measurement relative to the reference sensor | |||||
7 | Absolute pressure measurement | |||||
Index 8050 AI Settings Ch.3 (parameterization of channel 4)
Index (hex) | Name | Meaning | Data type | Flags | Default | |
|---|---|---|---|---|---|---|
8050:0 | AI Settings Ch.4 | Maximum subindex | UINT8 | RO | 0x19 (25dec) | |
8050:01 | Enable user scale | 1 | User scale is active. | BOOLEAN | RW | 0x00 (0dec) |
8050:06 | Enable filter | 1 | Enable filter, which makes PLC-cycle-synchronous data exchange unnecessary | BOOLEAN | RW | 0x01 (1dec) |
8050:07 | Enable limit 1 | 1 | Limit 1 enabled | BOOLEAN | RW | 0x00 (0dec) |
8050:08 | Enable limit 2 | 1 | Limit 2 enabled | BOOLEAN | RW | 0x00 (0dec) |
8050:0A | Enable user calibration | 1 | Enabling of the user calibration | BOOLEAN | RW | 0x00 (0dec) |
8050:0B | Enable vendor calibration | 1 | Enabling of the vendor calibration | BOOLEAN | RW | 0x01 (1dec) |
8050:11 | User scale offset | User scale offset | INT32 | RW | 0x00000000 (0dec) | |
8050:12 | User scale gain | User scale gain. | INT32 | RW | 0x00010000 (65536dec) | |
8050:13 | Limit 1 | First limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8050:14 | Limit 2 | Second limit value for setting the status bits | INT16 | RW | 0x0000 (0dec) | |
8050:15 | Filter settings | This object shows the digital filter settings. The filter settings can only be read here. They are set via channel 1 for all channels of the module. | UINT16 | RW | 0x0000 (0dec) | |
0 | 50 Hz FIR | |||||
1 | 60 Hz FIR | |||||
2 | IIR 1 | |||||
3 | IIR 2 | |||||
4 | IIR 3 | |||||
5 | IIR 4 | |||||
6 | IIR 5 | |||||
7 | IIR 6 | |||||
8 | IIR 7 | |||||
9 | IIR 8 | |||||
8050:17 | User calibration offset |
| INT32 | RW | 0x00000000 (0dec) | |
8050:18 | User calibration gain |
| INT16 | RW | 0x4000 (16384dec) | |
8050:19 | Range | Permissible values: | UINT16 | RW | 0x0008 (8dec) | |
8 | Differential pressure measurement relative to the reference sensor | |||||
7 | Absolute pressure measurement | |||||