0x80nE PAI User Calibration Ch.[n+1]

0 ≤ n ≤ m, n+1 = Channel number, m+1 = max. No. of channels

Index (hex)

Name

Meaning

Data type

Flags

Default

80nE:0

PAI User Calibration Data Ch.1

 

UINT8

RO

0x0C (12dec)

80nE:01

Calibration Date

Date of calibration

OCTET-STRING[4]

RW

-

80nE:02

Signature

Signature of the calibration values

OCTET-STRING[256]

RW

-

80nE:03

S0

Offset

REAL32

RW

0x00000000 (0.0dec)

80nE:04

S1

Coefficient for first-order samples
(S1 * sample)

REAL32

RW

0x3F800000 (1.0dec)

80nE:05

S2

Coefficient for second-order samples
(S2 * sample²)

REAL32

RW

0x00000000 (0.0dec)

80nE:06

S3

Coefficient for third-order samples
(S3 * sample³)

REAL32

RW

0x00000000 (0.0dec)

80nE:07

T1

Temperature coefficient for first-order temperature value
(T1 * temp)

REAL32

RW

0x00000000 (0.0dec)

80nE:08

T1S1

Combined coefficient for first-order gain and temperature values
(T1S1 * temp * sample)

REAL32

RW

0x00000000 (0.0dec)

80nE:09

T2

Temperature coefficient for second-order temperature value
(T2 * temp²)

REAL32

RW

0x00000000 (0.0dec)

80nE:0A

T2S1

Combined coefficient for second-order gain and temperature values
(T2S1 * temp² * sample)

REAL32

RW

0x00000000 (0.0dec)

80nE:0B

T3

Temperature coefficient for third-order temperature value
(T3 * temp³)

REAL32

RW

0x00000000 (0.0dec)

80nE:0C

T3S1

Combined coefficient for third-order gain and temperature values
(T3S1 * temp³ * sample)

REAL32

RW

0x00000000 (0.0dec)