Sample program 3 (write LookUp table)
Download TwinCAT 3 project: program link
Program description
Transmission of LookUp table interpolation values for mapping of an equation f(x) = x3 via CoE into the box module.
Variable declaration sample program 3
PROGRAM MAINVAR //LookUp-Table (LUT) generated by: MBE * x³ aLUT:ARRAY[0..99] OF DINT := [ -7812500,-7812500,-7493593,-6894382, -7174765,-6051169,-6855859,-5279674,-6536953,-4576709, -6218125,-3939087,-5899218,-3363620,-5580390,-2847120, -5261484,-2386402,-4942578,-1978275,-4623750,-1619555, -4304843,-1307052,-3985937,-1037580,-3667109,-807951, -3348203,-614978,-3029375,-455472,-2710468,-326248, -2391562,-224117,-2072734,-145892,-1753828,-88385, -1434921,-48409,-1116093,-22776,-797187,-8300, -478281,-1792,-159453,-66,159453,66, 478281,1792,797187,8300,1116093,22776, 1434921,48409,1753828,88385,2072734,145892, 2391562,224117,2710468,326248,3029375,455472, 3348203,614978,3667109,807951,3985937,1037580, 4304843,1307052,4623750,1619555,4942578,1978275, 5261484,2386402,5580390,2847120,5899218,3363620, 6218125,3939087,6536953,4576709,6855859,5279674, 7174765,6051169,7493593,6894382,7812500,7812500 ]; // For CoE 0x8000 and 0x8005 - write values: // =============================================== wCoEIndexScaler :WORD := 16#8005; // CoE Index wState :BYTE := 0; // Write status fb_coe_writeEx :FB_EcCoESdoWriteEx; // Function Block for writing in CoE userNetId :T_AmsNetId := '172.128.1.1.5.1'; // Have to be entered userSlaveAddr :UINT := 1003; // Have to be entered bWriteLUT2CoE :BOOL:=FALSE; // Sign for start writing bError :BOOL:=FALSE; // Sign for any errorEND_VARRemarks:
- The variable "startWrite" (BOOL) is also declared in sample program 4.
- The variable 'userNetId' must include the EtherCAT net ID of the device. It can be viewed in the "EtherCAT" tab under "Device (EtherCAT)".
- The variable "userSlaveAddr" must contain the EtherCAT address of the box module.
Sample program for transferring the LookUp table:
Execution part:
// Example program 3:// ###### Write LookUp table into CoE object 0x8005: #######IF bWriteLUT2CoE THENCASE wState OF 0: fb_coe_writeEx(bExecute := FALSE);// Prepare CoE-Access wState := wState + 1;// Next state 1: // Write 100 X/Y LookUp-Table entries fb_coe_writeEx( sNetId:= userNetId, nSlaveAddr:= userSlaveAddr, nSubIndex:= 1, nIndex:= wCoEIndexScaler, pSrcBuf:= ADR(aLUT), cbBufLen:= SIZEOF(aLUT), bCompleteAccess:= TRUE, bExecute:= TRUE ); wState := wState + 1; // Next state 2: // Proceed with writing to CoE fb_coe_writeEx(); IF NOT fb_coe_writeEx.bBusy THEN wState := 0;// Done bWriteLUT2CoE := FALSE; bError := fb_coe_writeEx.bError; // See nErrId if TRUE END_IFEND_CASEEND_IFA simple variable query, e.g., via button linked with bEnable, can be used to initiate the transfer. The variable declaration must contain
VAR_INPUT bEnable AT%I* :BOOL;END_VARand the following program lines:
IF bEnable AND NOT startWrite THEN bWriteLUT2CoE := TRUE;END_IF