Profile-specific objects (0x6000-0xFFFF)

The profile-specific objects have the same meaning for all EtherCAT slaves that support the profile 5001.

Index 6000: RTD Inputs Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

6000:0

RTD Inputs Ch.1

Maximum subindex

UINT8

RO

0x11 (17dec)

6000:01

Underrange

Is set if the value falls below the operating range of the sensor or the process record contains the lowest possible value.

BOOLEAN

RO

0x00 (0dec)

6000:02

Overrange

Is set if the value exceeds the operating range of the sensor or the process record contains the highest possible value.

BOOLEAN

RO

0x00 (0dec)

6000:03

Limit 1

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6000:05

Limit 2

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6000:07

Error

The error bit is set if the process data is invalid (wire breakage, overrange, underrange).

BOOLEAN

RO

0x00 (0dec)

6000:0E

Sync error

Only in DC: bit is set if the slave is not able to operate synchronous with master, because it cannot keep up with the cycle time.

BOOLEAN

RO

0x00 (0dec)

6000:0F

TxPDO State

Validity of the data of the associated TxPDO

BOOLEAN

RO

0x00 (0dec)

0

valid

1

invalid

6000:10

TxPDO Toggle

TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

6000:11

Value

Analog input date

INT16

RO

0x0000 (0dec)

Index 6010: RTD Inputs Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

6010:0

RTD Inputs Ch.2

Maximum subindex

UINT8

RO

0x11 (17dec)

6010:01

Underrange

Is set if the value falls below the operating range of the sensor or the process record contains the lowest possible value.

BOOLEAN

RO

0x00 (0dec)

6010:02

Overrange

Is set if the value exceeds the operating range of the sensor or the process record contains the highest possible value.

BOOLEAN

RO

0x00 (0dec)

6010:03

Limit 1

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6010:05

Limit 2

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6010:07

Error

The error bit is set if the process data is invalid (wire breakage, overrange, underrange).

BOOLEAN

RO

0x00 (0dec)

6010:0E

Sync error

Only in DC: bit is set if the slave is not able to operate synchronous with master, because it cannot keep up with the cycle time.

BOOLEAN

RO

0x00 (0dec)

6010:0F

TxPDO State

Validity of the data of the associated TxPDO

BOOLEAN

RO

0x00 (0dec)

0

valid

1

invalid

6010:10

TxPDO Toggle

TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

6010:11

Value

Analog input date

INT16

RO

0x0000 (0dec)

Index 6020: RTD Inputs Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

6020:0

RTD Inputs Ch.3

Maximum subindex

UINT8

RO

0x11 (17dec)

6020:01

Underrange

Is set if the value falls below the operating range of the sensor or the process record contains the lowest possible value.

BOOLEAN

RO

0x00 (0dec)

6020:02

Overrange

Is set if the value exceeds the operating range of the sensor or the process record contains the highest possible value.

BOOLEAN

RO

0x00 (0dec)

6020:03

Limit 1

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6020:05

Limit 2

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6020:07

Error

The error bit is set if the process data is invalid (cable break, overrange, underrange)

BOOLEAN

RO

0x00 (0dec)

6020:0E

Sync error

Only in DC: bit is set if the slave is not able to operate synchronous with master, because it cannot keep up with the cycle time.

BOOLEAN

RO

0x00 (0dec)

6020:0F

TxPDO State

Validity of the data of the associated TxPDO

BOOLEAN

RO

0x00 (0dec)

0

valid

1

invalid

6020:10

TxPDO Toggle

TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

6020:11

Value

Analog input date

INT16

RO

0x0000 (0dec)

Index 6030: RTD Inputs Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

6030:0

RTD Inputs Ch.4

Maximum subindex

UINT8

RO

0x11 (17dec)

6030:01

Underrange

Is set if the value falls below the operating range of the sensor or the process record contains the lowest possible value.

BOOLEAN

RO

0x00 (0dec)

6030:02

Overrange

Is set if the value exceeds the operating range of the sensor or the process record contains the highest possible value.

BOOLEAN

RO

0x00 (0dec)

6030:03

Limit 1

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6030:05

Limit 2

Only when limit check is active

BIT2

RO

0x00 (0dec)

1

Value below set limit

2

Set limit exceeded

3

Set limit reached

6030:07

Error

The error bit is set if the process data is invalid (wire breakage, overrange, underrange).

BOOLEAN

RO

0x00 (0dec)

6030:0E

Sync error

Only in DC: bit is set if the slave is not able to operate synchronous with master, because it cannot keep up with the cycle time.

BOOLEAN

RO

0x00 (0dec)

6030:0F

TxPDO State

Validity of the data of the associated TxPDO

BOOLEAN

RO

0x00 (0dec)

0

valid

1

invalid

6030:10

TxPDO Toggle

TxPDO toggle is toggled by the slave when the data of the associated TxPDO is updated.

BOOLEAN

RO

0x00 (0dec)

6030:11

Value

Analog input date

INT16

RO

0x0000 (0dec)

Index 800E: RTD Internal data Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

800E:0

RTD Internal data Ch.1

Maximum subindex

UINT8

RO

0x04 (4dec)

800E:01

ADC raw value 1

Raw value of the analog/digital converter

INT32

RO

0x00000000 (0dec)

800E:02

Resistor 1

Resistance value of the first measurement

UINT16

RO

0x0000 (0dec)

800E:03

ADC raw value 2

Raw value of the analog/digital converter

INT32

RO

0x00000000 (0dec)

800E:04

Resistor 2

Resistance value of the second measurement

UINT16

RO

0x0000 (0dec)

Index 800F: RTD Vendor data Ch.1

Index (hex)

Name

Meaning

Data type

Flags

Default

800F:0

RTD Vendor data Ch.1

Maximum subindex

UINT8

RO

0x07 (7dec)

800F:01

Calibration offset 3-wire

Calibration for 3-wire measurement: Offset

INT16

RW

0x0000 (0dec)

800F:02

Calibration gain 3-wire

Calibration for 3-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

800F:03

Calibration offset 2-wire

Calibration for 2-wire measurement: Offset

INT16

RW

0x0000 (0dec)

800F:04

Calibration gain 2-wire

Calibration for 2-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

800F:05

Calibration offset 4-wire

Calibration for 4-wire measurement: Offset

INT16

RW

0x0000 (0dec)

800F:06

Calibration gain 4-wire

Calibration for 4-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

800F:07

PGA Gain Correction

Gain correction for Pt1000 measurement

INT16

RW

0x0000 (0dec)

Index 801E: RTD Internal data Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

801E:0

RTD Internal data Ch.2

Maximum subindex

UINT8

RO

0x04 (4dec)

801E:01

ADC raw value 1

Raw value of the analog/digital converter

INT32

RO

0x00000000 (0dec)

801E:02

Resistor 1

Resistance value of the first measurement

UINT16

RO

0x0000 (0dec)

801E:03

ADC raw value 2

Raw value of the analog/digital converter

INT32

RO

0x00000000 (0dec)

801E:04

Resistor 2

Resistance value of the second measurement

UINT16

RO

0x0000 (0dec)

Index 801F: RTD Vendor data Ch.2

Index (hex)

Name

Meaning

Data type

Flags

Default

801F:0

RTD Vendor data Ch.2

Maximum subindex

UINT8

RO

0x07 (7dec)

801F:01

Calibration offset 3-wire

Calibration for 3-wire measurement: Offset

INT16

RW

0x0000 (0dec)

801F:02

Calibration gain 3-wire

Calibration for 3-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

801F:03

Calibration offset 2-wire

Calibration for 2-wire measurement: Offset

INT16

RW

0x0000 (0dec)

801F:04

Calibration gain 2-wire

Calibration for 2-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

801F:05

Calibration offset 4-wire

Calibration for 4-wire measurement: Offset

INT16

RW

0x0000 (0dec)

801F:06

Calibration gain 4-wire

Calibration for 4-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

801F:07

PGA Gain Correction

Gain correction for Pt1000 measurement

INT16

RW

0x0000 (0dec)

Index 802E: RTD Internal data Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

802E:0

RTD Internal data Ch.3

Maximum subindex

UINT8

RO

0x04 (4dec)

802E:01

ADC raw value 1

Raw value of the analog/digital converter

INT32

RO

0x00000000 (0dec)

802E:02

Resistor 1

Resistance value of the first measurement

UINT16

RO

0x0000 (0dec)

802E:03

ADC raw value 2

Raw value of the analog/digital converter

INT32

RO

0x00000000 (0dec)

802E:04

Resistor 2

Resistance value of the second measurement

UINT16

RO

0x0000 (0dec)

Index 802F: RTD Vendor data Ch.3

Index (hex)

Name

Meaning

Data type

Flags

Default

802F:0

RTD Vendor data Ch.3

Maximum subindex

UINT8

RO

0x07 (7dec)

802F:01

Calibration offset 3-wire

Calibration for 3-wire measurement: Offset

INT16

RW

0x0000 (0dec)

802F:02

Calibration gain 3-wire

Calibration for 3-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

802F:03

Calibration offset 2-wire

Calibration for 2-wire measurement: Offset

INT16

RW

0x0000 (0dec)

802F:04

Calibration gain 2-wire

Calibration for 2-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

802F:05

Calibration offset 4-wire

Calibration for 4-wire measurement: Offset

INT16

RW

0x0000 (0dec)

802F:06

Calibration gain 4-wire

Calibration for 4-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

802F:07

PGA Gain Correction

Gain correction for Pt1000 measurement

INT16

RW

0x0000 (0dec)

Index 803E: RTD Internal data Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

803E:0

RTD Internal data Ch.4

Maximum subindex

UINT8

RO

0x04 (4dec)

803E:01

ADC raw value 1

Raw value of the analog/digital converter

INT32

RO

0x00000000 (0dec)

803E:02

Resistor 1

Resistance value of the first measurement

UINT16

RO

0x0000 (0dec)

803E:03

ADC raw value 2

Raw value of the analog/digital converter

INT32

RO

0x00000000 (0dec)

803E:04

Resistor 2

Resistance value of the second measurement

UINT16

RO

0x0000 (0dec)

Index 803F: RTD Vendor data Ch.4

Index (hex)

Name

Meaning

Data type

Flags

Default

803F:0

RTD Vendor data Ch.4

 

UINT8

RO

0x07 (7dec)

803F:01

Calibration offset 3-wire

Calibration for 3-wire measurement: Offset

INT16

RW

0x0000 (0dec)

803F:02

Calibration gain 3-wire

Calibration for 3-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

803F:03

Calibration offset 2-wire

Calibration for 2-wire measurement: Offset

INT16

RW

0x0000 (0dec)

803F:04

Calibration gain 2-wire

Calibration for 2-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

803F:05

Calibration offset 4-wire

Calibration for 4-wire measurement: Offset

INT16

RW

0x0000 (0dec)

803F:06

Calibration gain 4-wire

Calibration for 4-wire measurement: Gain

UINT16

RW

0x4000 (16384dec)

803F:07

PGA Gain Correction

Gain correction for Pt1000 measurement

INT16

RW

0x0000 (0dec)

Index F000: Modular device profile

Index (hex)

Name

Meaning

Data type

Flags

Default

F000:0

Modular device profile

Maximum subindex

UINT8

RO

0x02 (2dec)

F000:01

Module index distance

Index spacing for the objects of the individual channels

UINT16

RO

0x0010 (16dec)

F000:02

Maximum number of modules

Number of channels

UINT16

RO

0x0004 (4dec)

Index F008: Code word

Index (hex)

Name

Meaning

Data type

Flags

Default

F008:0

Code word

reserved

UINT32

RW

0x00000000 (0dec)

Index F010: Module list

Index (hex)

Name

Meaning

Data type

Flags

Default

F010:0

Module list

Maximum subindex

UINT8

RW

0x04 (4dec)

F010:01

SubIndex 001

 

UINT32

RW

0x00000140 (320dec)

F010:02

SubIndex 002

 

UINT32

RW

0x00000140 (320dec)

F010:03

SubIndex 003

 

UINT32

RW

0x00000140 (320dec)

F010:04

SubIndex 004

 

UINT32

RW

0x00000140 (320dec)

Index F080: Channel Enable

Index (hex)

Name

Meaning

Data type

Flags

Default

F080:0

Channel Enable

Maximum subindex

UINT8

RO

0x04 (4dec)

F080:01

SubIndex 001

0

Channel 1 disabled

(from hardware version 01 deactivated channels are not measured, and the green LED R for these channels goes out)

BOOLEAN

RW

0x01 (1dec)

1

Channel 1 enabled

F080:02

SubIndex 002

0

Channel 2 disabled

BOOLEAN

RW

0x01 (1dec)

1

Channel 2 enabled

F080:03

SubIndex 003

0

Channel 3 disabled

BOOLEAN

RW

0x01 (1dec)

1

Channel 3 enabled

F080:04

SubIndex 004

0

Channel 4 disabled

BOOLEAN

RW

0x01 (1dec)

1

Channel 5 enabled