Technical data
All values are typical values over the entire temperature range, unless stated otherwise.
Supply voltages | |
|---|---|
Connection | See EtherCAT P connection |
|
US nominal voltage |
24 VDC (-15 % / +20 %) |
|
US sum current: IS,sum |
max. 3 A |
|
Current consumption from US |
100 mA |
Rated voltage UP | 24 VDC (-15 % / +20 %) |
|
UP sum current: IP,sum |
max. 3 A |
Current consumption from UP | 20 mA + Output currents of the digital outputs + sensor supply |
Digital inputs | EPP2339 | EPP2339 | EPP2349 | EPP2349 |
|---|---|---|---|---|
Number | max. 16 Each digital input can alternatively be used as a digital output. | |||
Connection | 16 x M8 socket | 8x M12 socket | 16 x M8 socket | 8x M12 socket |
Cable length | max. 30 m | |||
Characteristics | Type 3 according to EN 61131-2, compatible with type 1 | |||
Input filter | 3 ms | 3 ms | 10 µs | 10 µs |
Signal voltage "0" | -3 … +5 VDC | |||
Signal voltage "1" | +11 … +30 VDC | |||
Input current | 6 mA at 24 VDC | |||
Sensor power supply | 24 VDC from UP, | |||
Digital outputs | EPP2339 | EPP2339 | EPP2349 | EPP2349 |
|---|---|---|---|---|
Number | max. 16 Each digital output can alternatively be used as a digital input. | |||
Connection | 16 x M8 socket | 8x M12 socket | 16 x M8 socket | 8x M12 socket |
Cable length | max. 30 m | |||
Sensor power supply | 24 VDC from UP, | |||
Nominal voltage | 24 VDC from UP | |||
Load type | ohmic, inductive, lamp load | |||
Output current | max. 0.5 A per channel max. 3.0 A in total | |||
Short circuit current | max. 1.5 A per channel | |||
Switching times | TON: 60 µs typ., TOFF: 300 µs typ. | |||
Housing data | |
|---|---|
Dimensions W x H x D | 60 mm x 126 mm x 26.5 mm (without plug connectors) |
Weight | approx. 250 g |
Installation position | variable |
|
Material |
PA6 (polyamide) |
Environmental conditions | |
|---|---|
Ambient temperature during operation | -25 … +60 °C |
Ambient temperature during storage | -40 … +85 °C |
Vibration resistance, shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP65, IP66, IP67 (conforms to EN 60529) |
Approvals / markings | |
|---|---|
Approvals / markings *) | CE, cULus |
*) Real applicable approvals/markings see type plate on the side (product marking).
Additional tests
The devices have undergone the following additional tests:
Test | Explanation |
|---|---|
Vibration | 10 frequency sweeps in 3 axes |
5 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude | |
60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude | |
Shocks | 1000 shocks in each direction, in 3 axes |
35 g, 11 ms |