Behavior in case of short circuit

You can set the behavior of the outputs in case of short circuit in the CoE object F800 "DO Settings".

F800:0 - DO Settings (Safe State Value)

Behavior in case of short circuit 1:
F800:01 - Disable shut off (default: FALSE)

Value

Meaning

FALSE

In the event of a short circuit at one output, all outputs of the module are switched off.
This disabling can be removed through the process data value Reset Outputs.

TRUE

In the event of a short circuit at an output, only this output of the module is switched off.
After rectifying the short circuit, this output is automatically enabled again.

F800:11 - Switch off time (default: 0x03E8, 1000dec)

Here you can enter a time in milliseconds. During this time, the module checks whether the short circuit has been eliminated by switching itself on again.
Default = 1000 ms (depending on module type and internal cycle time). Errors are only displayed after this time.