- EP/EPP1518-0002 - 8 inputs, 2 counters
- Product overview
- Process image
Process image
The process image depends on the selected operation mode.
Operation mode: 2 counters and 2 digital inputs (delivery state)
| The input data of the 1st counter can be found under CNT Input Channel 1.
- Set counter done indicates the transfer of the Set counter bit from CNT Output Channel 1.
- Counter inhibited indicates the transfer of the Inhibit counter bit from CNT Output Channel 1.
- Status of input UD shows the status of the Up/Down counter input of the 1st counter.
- Status of input clock shows the status of the input clock input of the 1st counter.
- Sync Error, TxPDO State and TxPDO Toggle are standard EtherCAT process data.
The input data of the 2st counter can be found under CNT Input Channel 2. Its structure corresponds to that of the first counter.
DIG Inputs shows the states of the individual inputs irrespective of the selected operation mode. Assignment of port names to variable names.
DIG Inputs Device
- Error channel 1 indicates a short circuit of the supply voltage US at the digital inputs X01 to X04.
- Error channel 2 indicates a short circuit of the supply voltage US at the digital inputs X05 to X08.
The output data of the 1st counter can be found under CNT Output Channel 1.
- The setting of Set counter activates the adoption of the Set Counter Value into the Counter Value of the 1st counter.
- The setting of Inhibit Counter disables the 1st counter.
Alternatively the counter can be disabled or enabled by the physical GATE input. The two values are XORed.
The output data of the 2nd counter can be found under CNT Output Channel 1. Its structure corresponds to that of the first counter.
|
Operation mode: 1 counter and 5 digital inputs

| The input data of the 1st counter can be found under CNT Input Channel 1.
- Set counter done indicates the transfer of the Set counter bit from CNT Output Channel 1.
- Counter inhibited indicates the transfer of the Inhibit counter bit from CNT Output Channel 1.
- Status of input UD shows the status of the Up/Down counter input of the 1st counter.
- Status of input clock shows the status of the input clock input of the 1st counter.
- Sync Error, TxPDO State and TxPDO Toggle are standard EtherCAT process data.
DIG Inputs shows the states of the individual inputs irrespective of the selected operation mode. Assignment of port names to variable names.
DIG Inputs Device
- Error channel 1 indicates a short circuit of the supply voltage US at the digital inputs X01 to X04.
- Error channel 2 indicates a short circuit of the supply voltage US at the digital inputs X05 to X08.
The output data of the 1st counter can be found under CNT Output Channel 1.
- The setting of Set counter activates the adoption of the Set Counter Value into the Counter Value of the 1st counter.
- The setting of Inhibit Counter disables the 1st counter.
Alternatively the counter can be disabled or enabled by the physical GATE input. The two values are XORed.
|
Operation mode: 8 digital inputs
| DIG Inputs shows the states of the individual inputs irrespective of the selected mode. Assignment of port names to variable names.
DIG Inputs Device
- Error channel 1 indicates a short circuit of the supply voltage US at the digital inputs X01 to X04.
- Error channel 2 indicates a short circuit of the supply voltage US at the digital inputs X05 to X08.
|