Technical Data

All values are typical values over the entire temperature range, unless stated otherwise.

Fieldbus

Protocol

EtherCAT / Industrial Fast Ethernet

Copper connection

2 x M8 socket, 4-pin, A-coded, shielded

Fiber optic connection

1 x LC duplex

For IP67 use: only use HARTING "PushPull LC Duplex"

Data transfer medium: copper

Ethernet / EtherCAT cable (min. Cat.5), shielded

Data transfer medium: fiber optic

Multi-mode glass fiber 50/125 µm

Copper cable length

max. 100 m, twisted pair or star quad CAT5(e)

Fiber optic cable length

max. 2000 m (100BASE-FX)

EtherCAT function

Fast Ethernet / 100 Mbaud media converter

  • Cut-through switching
  • Port handling/link control

Ethernet function

Fast Ethernet / 100 Mbaud media converter
(all protocols based on IEEE 802.3)

  • IEEE 802.3u auto-negotiation, half or full duplex, automatic settings
  • Link Loss Forwarding (notification direction configurable)
  • Store and Forward Mode (FIFO)
  • Unmanaged

Propagation delay

approx. 1 µs

Electrical isolation

500 V

Optical data of the fiber-optic connection

Transceiver wavelength

typically 1310 nm

Minimum output power

-23.5 dBm avg. (50/125 µm, NA = 0.2)

Maximum output power

-14 dBm

Maximum sensitivity

(Minimum required input power)

-31 dBm

Maximum permissible input power

-14 dBm

Supply voltages

Connection

Input: M8 connector, 4-pin, A-coded

Downstream connection: M8 socket, 4-pin, A-coded

US nominal voltage

24 VDC (-15 % / +20 %)

US sum current: IS,sum

max. 4 A

Current consumption from US

120 mA

Rated voltage UP

24 VDC (-15 % / +20 %)

UP sum current: IP,sum

max. 4 A

Current consumption from UP

None. UP is only forwarded.

Housing data

Dimensions W × H × D

85 mm x 126 mm x 26.5 mm (without connector)

Weight

300 g

Installation position

variable

Material

PA6 (polyamide)

Environmental conditions

Ambient temperature during operation

-25 … +60 °C
-25 … +55 °C according to cURus

Ambient temperature during storage

-40 … +85 °C

Vibration resistance, shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27
Additional tests

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP65, IP66, IP67 (conforms to EN 60529)

Approvals/markings

Approvals/markings *)

CE, cURus

*) Real applicable approvals/markings see type plate on the side (product marking).

Additional tests

The devices have undergone the following additional tests:

Test

Explanation

Vibration

10 frequency sweeps in 3 axes

5 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude

60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude