LED display

EtherCAT Link/Act

LED

Display

Meaning

Link/Act

off

No connection to the following EtherCAT module.

green illuminated

Link: connection to the following EtherCAT module.

green flashing

Act: Communication with the following EtherCAT module.

Profinet status

LED

Display

Meaning

RUN

green illuminated

EP9300-0022 is ready.

red illuminated

May only light up during the start-up phase

PN

red flashing (200 ms)

Start-up phase

green flashing
(200 ms)

No Profinet name

green flashing
(1 s off, 200 ms on)

No IP address

green illuminated

OK

DIAG

red/green flashing
(500 ms)

Profinet controller identification:
The Profinet controller is transmitting an identification signal.

red flashing
(200 ms)

No AR established:
The establishment of a connection with the controller has not been completed.

green flashing
(1 s off, 200 ms on)

Problem with establishment of a connection or nominal and actual configuration differ.

green flashing (200 ms)

EP9300-0022 is in data exchange, but PLC is in stop

green illuminated

OK

Profinet Link/Act

LED

Display

Meaning

L/A

off

no connection to the next Profinet module

green illuminated

Link: connection to the next Profinet module

green flashing

Activity: communication with the next Profinet module

Supply voltage status

LED

Display

Meaning

Us 24 V

off

The power supply voltage Us is not present

green illuminated

The power supply voltage Us is present

Up 24 V

off

The power supply voltage Up is not present

green illuminated

The power supply voltage Up is present