Configure overload switch-off

You can configure the overload switch-off for each output voltage individually.

The configuration of the overload switch-off is similar to the selection of a fuse: you select the nominal current and the tripping characteristic.

The nominal current can be set between 1000 and 4000 mA.

Connection

Nominal current in mA

Tripping characteristic

1

8000:12 „Nominal Current Us

8000:13 „Nominal Current Up

8000:11 „Characteristic

2

8010:12 „Nominal Current Us

8010:13 „Nominal Current Up

8010:11 „Characteristic

3

8020:12 „Nominal Current Us

8020:13 „Nominal Current Up

8020:11 „Characteristic

4

8030:12 „Nominal Current Us

8030:13 „Nominal Current Up

8030:11 „Characteristic

If the nominal current is exceeded, the status bit "Warning" is set.

Examples of maximum switch-off times

The following table shows the maximum switch-off time of the overload switch-off for different currents and tripping characteristics.

Configure overload switch-off 1:

Shorter switch-off time with current limitation

The switch-off times shown only apply to output currents below the current limit.

If the current limitation is active, the output may be switched off earlier than the configured switch-off time.

EP92x4-0023 from firmware 20 and EP92x4-0024:

% of the nominal current

Very fast acting

Fast acting

Slow acting

Time delay

105 %

3600 s

3600 s

3600 s

3600 s

135 %

420 s

3600 s

3600 s

3600 s

200 %

0.5 s

20 s

20 s

100 s

300 %

0.02 s

0.1 s

1 s

3 s

EP92x4-0023 with firmware below 20:

Nominal current

Very fast acting

Fast acting

Slow acting

Time delay

100 %

1 h

-

-

-

110 %

1 h

4 h

-

-

120 %

7 min

4 h

-

-

150 %

30 s

30 min

1 h

4 h

210 %

500 ms

20 s

20 s

100 s

275 %

500 ms

1 s

20 s

10 s

300 %

20 ms

100 ms

1 s

3 s