Troubleshooting with the data logger

You can use the data logger to determine the cause of an error, among other things. The prerequisite for this is that the recording of the measured values is already enabled when the error occurs.

Determine the cause of the error

The data logger stops recording the measured values if an error occurs, among other things. The reason for the last stop of the recording is output in the process data and via a CoE parameter:

Possible values:

Value

Enum text

Reason for stopping the recording

0

Undefined

Unknown.

1

Undervoltage Us

Undervoltage of US.

2

Undervoltage Up

Undervoltage of UP.

3

Overtemperature

Internal temperature too high.

4

Overcurrent

The overload switch-off has switched off an output voltage.

5

FoE Transfer

The data upload was started before the recording was stopped.

6

Hardware Protection

Thermal shutdown of an output voltage after current limitation.

7

User Stop Bit

Set the bit "Stop Logger" in the process data.

255

Logger still running

N/A. The recording has not yet been stopped.