Technical data

All values are typical values over the entire temperature range, unless stated otherwise.

EtherCAT

Connection

2 x M8 socket, 4-pin, green

Electrical isolation

500 V

Supply voltages

Connection

Input: 7/8" - plug, 5-pin

Downstream connection: 7/8" - socket, 5-pin

US nominal voltage

24 VDC (-15 % / +20 %)

US sum current 1)

max. 16 A at 40 °C

Current consumption from US

110 mA

+ sum of the output currents

Rated voltage UP

24 VDC (-15 % / +20 %)

UP sum current 1)

max. 16 A at 40 °C

Current consumption from UP

40 mA

+ sum of the output currents

1) This value corresponds to the current carrying capacity of the connectors.

 

Outputs

Number

4

Connection

4 x M8 socket, black

Output current per M8 socket

max. 4 A per US and UP

Parallel switching of outputs

not permissible

Voltage drop UON

90 mV per ampere

Inrush delay 2)

adjustable: 10 ms, 100 ms, 200 ms

2) The output voltages are switched on one after the other at the start so that the
   input inrush currents do not add up.

 

Protective functions and diagnostics

EP9214-0023

EP9224-0023

Overcurrent tripping characteristic

Individually adjustable for each output.

Temperature switch-off

85 °C internal temperature

Internal fuse
(fail-safe element)

7 A (FF)

Data logging

-

40 entries

Sample time: 1...1000 ms

Reset contact and signaling contact

Connection

M8 connector X3: 3-pin, black

M8 socket X4: 3-pin, black

Reset contact

Digital input, nominal voltage: 24 VDC

Signaling contact

Potential-free NO contact

Measured values

EP9214-0023

EP9224-0023

Representation

-

Measured current values:

  • Output currents per channel: 1 mA / LSB
  • Sum currents: 10  mA / LSB

Measured voltage values: 100 mV / LSB

Resolution

-

Measured current values: 10 mA

Measured voltage values: 100 mV

Accuracy

-

5 % of full scale value

Housing data

Dimensions W x H x D

60 mm x 150 mm x 26,5 mm (without connectors)

Weight

approx. 440 g

Material

PA6 (polyamide)

Installation position

variable

Environmental conditions

Ambient temperature during operation

-25…+60 °C

Ambient temperature during storage

-40…+85 °C

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity / emission

conforms to EN 61000-6-2 / EN 61000-6-4

Protection class

IP65, IP66, IP67 conforms to EN 60529

Approvals / markings

Approvals / markings *)

CE, UL under preparation

*) Real applicable approvals/markings see type plate on the side (product marking).