Status LEDs and status bits

Below is a table showing the meaning of the Status LEDs and Status bits for the power outputs (taking the EP9214 as an example):

Status LEDs and status bits 1:
EP9214 - Status LEDs
Status LEDs and status bits 2:
EP9214 - Status bits

The LED applies to both voltages/currents (Us and Up; OR).

LED

Status
Us / Up

Warning

Error
Us / Up

Description

Off

0

0

0

The output is ready

Green

1

0

0

The output is just switching on

Green

1

0

0

The output is switched on. Normal operating state.

Flashing green

1

1

0

The output is still operating, but will switch off if conditions remain unchanged (Warning Ux).

Flashing red

0

1

1

The output has been switched off (Error Ux). Switching on again is not yet possible (waiting time of 20 seconds)

Red

0

0

1

The output has been disabled and can be returned to a normal state by a reset.

Red running light all channels

x

1

1

Undervoltage Us/Up or temperature error

Initialization

When switching on the voltage supply to the EP9214 / EP9224, all green LEDs and then all red LEDs are switched on briefly to test the LEDs.