Technical data
All values are typical values over the entire temperature range, unless stated otherwise.
EtherCAT | |
|---|---|
Input | B17 ENP, connection X70 |
Downstream connection | B17 ENP, connection X71 |
Outputs | 4x M8 socket, 4-pin, green, connections X40 ... X43 |
Electrical isolation | 500 V |
Supply voltage input and downstream connection | |
|---|---|
Input | Plug B17 5G 1.5mm² ENP, connection X70 |
Downstream connection | Socket B17 5G 1.5mm² ENP, connection X71 |
US nominal voltage | 24 VDC (-15 % / +20 %) |
US sum current | max. 15.5 A at 45 °C |
Current consumption from US | 110 mA + load |
UP nominal voltage | 24 VDC (-15 % / +20 %) |
UP sum current | max. 15.5 A at 45 °C |
Current consumption from UP | 40 mA + load |
Supply voltage outputs | |
|---|---|
Number | 4 |
Connection | 4x M8 socket, 4-pin, black |
Cable length | max. 30 m |
Output current per channel | max. 4 A per US and UP. |
Output current limitation per channel | 4.4 A per US and UP. |
Output power limitation per channel | 100 W per US and UP. |
Overload switch-off | Configurable, see chapter Overload protection. |
Fuse (faile-safe element) | Fuse 7 A according to UL 248-1 |
Capacitive load per channel | 2200 µF per US and UP (This value is provisional. The actual possible capacitive load is likely to be higher) |
Switch-on time delay of the channels | Adjustable, see chapter Switch output voltages.
|
Total power loss | max. 12 W at full load. (4 A output current per US and UP at all outputs at 24 VDC supply voltage)
|
Protective functions and diagnostics | |
|---|---|
Overtemperature protection | Threshold values: Twarn = 75 °C → Warning if exceeded |
Undervoltage protection | Threshold values: Uwarn = 21.6 V → Warning when falling below |
Data logger: sampling interval |
|
Data logger: buffer size | 25 entries. |
Measured values | |
|---|---|
Resolution | Measured current values: 10 mA Measured sum current values US + UP: 10 mA Measured voltage values: 100 mV Measured temperature values: 1 K |
Representation | Measured current values: 1 mA / LSB Measured sum current values US + UP: 10 mA / LSB Measured voltage values: 100 mV / LSB Measured temperature values: 1 K / LSB (Celsius scale) |
|
Housing data | |
|---|---|
|
Dimensions W x H x D |
60 mm x 150 mm x 26,5 mm (without connectors) |
Weight | approx. 540 g |
Installation position | variable |
|
Material |
PA6 (polyamide) |
Environmental conditions | |
|---|---|
Ambient temperature during operation | -25 … +60 °C |
Ambient temperature during storage | -40 … +85 °C |
Vibration resistance, shock resistance | conforms to EN 60068-2-6 / EN 60068-2-27 |
EMC immunity / emission | conforms to EN 61000-6-2 / EN 61000-6-4 |
Protection class | IP65, IP66, IP67 (conforms to EN 60529) |
Approvals / markings | |
|---|---|
Approvals / markings *) | CE, UL under preparation |
*) Real applicable approvals/markings see type plate on the side (product marking).
Additional tests
The devices have undergone the following additional tests:
Test | Explanation |
|---|---|
Vibration | 10 frequency sweeps in 3 axes |
5 Hz < f < 60 Hz displacement 0.35 mm, constant amplitude | |
60.1 Hz < f < 500 Hz acceleration 5 g, constant amplitude | |
Shocks | 1000 shocks in each direction, in 3 axes |
35 g, 11 ms |