Configure overload switch-off

You can configure the overload switch-off for each output voltage individually.

The configuration of the overload switch-off is similar to the selection of a fuse: you select the rated current and the tripping characteristic.

The rated current can be set between 1000 and 3000 mA.

Port

Rated current in mA

Tripping characteristic

X52

8000:12 „Nominal Current Us“

8000:13 „Nominal Current Up“

8000:11 „Characteristic“

X53

8010:12 „Nominal Current Us“

8010:13 „Nominal Current Up“

8010:11 „Characteristic“

X54

8020:12 „Nominal Current Us“

8020:13 „Nominal Current Up“

8020:11 „Characteristic“

X55

8030:12 „Nominal Current Us“

8030:13 „Nominal Current Up“

8030:11 „Characteristic“

If the rated current is exceeded, the status bit "Warning" is set.

Examples of the switch-off time

The following table shows the maximum switch-off time of the overload switch-off for different currents and tripping characteristics.

Configure overload switch-off 1:

Shorter switch-off time with current limitation

The switch-off times shown only apply to output currents below the current limit.

If the output current is so high that the current limitation becomes active, the shutdown takes place after the thermal switch-off time. The thermal switch-off time cannot be configured and is usually shorter than the configured switch-off time.

From Firmware 20

% of the nominal current

Very fast acting

Fast acting

Slow acting

Time delay

105 %

3600 s

3600 s

3600 s

3600 s

135 %

420 s

3600 s

3600 s

3600 s

200 %

0.5 s

20 s

20 s

100 s

300 %

0.02 s

0.1 s

1 s

3 s

Up to firmware 03

Nominal current

Very fast acting

Fast acting

Slow acting

Time delay

100 %

1 h

-

-

-

110 %

1 h

4 h

-

-

120 %

7 min

4 h

-

-

150 %

30 s

30 min

1 h

4 h

210 %

500 ms

20 s

20 s

100 s

275 %

500 ms

1 s

20 s

10 s

300 %

20 ms

100 ms

1 s

3 s